Sanyo SPWXDR124GH56A Manual Del Usuario página 45

Tabla de contenido

Publicidad

CAUTION
(1) When linking the outdoor units in a network (S-net link system), disconnect the terminal extended
from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all
outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no
wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address
setting.
Outdoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches that are less than 1 m are not included in the total branch number.) (Fig. 5-3)
Branch
point
16 or fewer
DC̲Inverter̲Eng.indd 45
DC̲Inverter̲Eng.indd 45
Outdoor unit
Indoor unit
Indoor unit
Fig. 5-1
Indoor unit
Indoor unit
Fig. 5-2
Outdoor unit
Outdoor unit
Indoor unit
Indoor unit
more than 1 m
Indoor unit
Indoor unit
more than 1 m
Indoor unit
less than 1 m
Indoor unit
Fig. 5-3
45
Outdoor unit
Prohibited
Prohibited
Indoor unit
Outdoor unit
NO
Indoor unit
Indoor unit
Branch point
Outdoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
Indoor unit
2007/07/25 13:21:43
2007/07/25 13:21:43
GB
FR
DE
IT
PT
GR
ES

Publicidad

Tabla de contenido
loading

Tabla de contenido