CAUTION
(1) When linking the outdoor units in a network (S-net link system), disconnect the terminal extended
from the short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all
outdoor units except any one of the outdoor units.
(When shipping: In shorted condition.)
Otherwise the communication of S-net link system is not performed. For a system without link (no
wiring connection between outdoor units), do not remove the short plug.
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)
Outdoor unit
Indoor unit
(3) Do not install inter-unit control wiring such as star
branch wiring. Star branch wiring causes mis-address
setting.
Outdoor unit
NO
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.
(Branches that are less than 1 m are not included in the total branch number.) (Fig. 5-3)
Branch
point
16 or fewer