Wiring The Remote Controller - Sanyo SPWXDR124GH56A Manual Del Usuario

Tabla de contenido

Publicidad

6-6. Wiring the Remote Controller

<Flush Mounting>
● Connection diagram
● Use 0.5 mm
2
– 2 mm
(1) Strip the insulation to approximately 14 mm from
the ends of the wires that will be connected.
(2) Twist together the 2 wires and create a crimp
connection at the wire joint.
(3) If a special crimping tool is not used, or if the
connection is soldered, insulate the wires using
insulation tape.
● Use the remote controller cord (optional) for remote
controller wiring.
(1) Disconnect the lead wire that is wound around the
lead wire anchor on the remote controller unit.
Disconnect the connector and connect the remote
controller cord (optional) to the connector on the
remote controller unit. Insert the remote controller
cord (optional) into the groove and bend it into the
correct shape, then wind it around the lead wire
anchor.
(2) If the remote controller cord (optional) is used,
refer to the installation manual that is provided
with the cord.
DC̲Inverter̲Eng.indd 51
DC̲Inverter̲Eng.indd 51
Terminal board for
1
indoor unit remote
2
controller wiring
Remote controller wiring
(field supply)
2
wires.
Approx.
200 mm
Remote
W
1
controller
2
BK
unit
Connector
Power wire from remote
controller unit
Provided wire joint
(white)
Remote controller wiring
Power wire from
remote controller
unit
Lead wire anchor
Connector
51
Wire joint
CE-1, white
Remote controller cord (optional)
2007/07/25 13:21:45
2007/07/25 13:21:45
GB
FR
DE
IT
PT
GR
ES

Publicidad

Tabla de contenido
loading

Tabla de contenido