10-4. Items to Check Before the Test Run
(1) Turn the remote power switch ON at least 12 hours in advance in order to energize the crank case heater.
(2) Fully open the closed valves on the liquid-tube and gas-tube sides.
10-5. Test Run Using the Remote Controller
GB
(1) Press and hold the remote controller
"TEST" appears in the LCD display during the test run.
Temperature control is not possible when test run mode is engaged.
(This mode places a large load on the devices. Use it only when performing the test run.)
FR
(2) Use either Heating or Cooling mode to perform the test run.
Note: The outdoor unit will not operate for approximately 3 minutes after the power is turned ON or after it stops
operating.
(3) If normal operation is not possible, a code appears on the remote controller LCD display.
DE
Refer to the "Table of Self-Diagnostic Functions and Corrections" on the next page, and correct the problem.
(4) After the test run is completed, press the
display.
(This remote controller includes a function that cancels test run mode after a 60-minute timer has elapsed, in
IT
order to prevent continuous test run operation.)
(5) For the test run of an inverter outdoor unit, operate the compressors for a minimum of 10 minutes (in order to
check for open phase).
* When performing a test run using a wired remote controller, operation is possible without attaching the
PT
cassette-type ceiling panel.
("P09" will not be displayed.)
10-6. Precautions
GR
Request that the customer be present when the test run is performed. At this time, explain the operation manual
and have the customer perform the actual steps.
Be sure to pass the manuals and warranty certificate to the customer.
Check that the 220 – 240 V AC power is not connected to the inter-unit control wiring connector terminal.
ES
* If 220 – 240 V AC is accidentally applied, the indoor or outdoor unit control PCB fuse (0.5 A for indoor units,
0.4 A for outdoor units) will blow in order to protect the PCB. Correct the wiring connections, then disconnect
the 2P connectors (indoor and outdoor: blue, OC) that are connected to the PCB, and replace them with 2P
connectors (indoor and outdoor: blue, EMG). (Refer to the figure below.) If operation is still not possible after
changing the brown connectors, try cutting the varistor (indoor: VA100, outdoor: JP007).
(Be sure to turn the power OFF before performing this work.)
Indoor unit control PCB
Varistor (black)
VA100
Fuse 0.5A
DC̲Inverter̲Eng.indd 68
DC̲Inverter̲Eng.indd 68
button for 4 seconds or longer. Then press the
button again. Check that "TEST" disappears from the LCD
Outdoor unit control PCB
CHK (2P plug)
2P connector (brown)
4 – 6 HP
2P connector (blue)
F101
MOV
(CN025, WHT)
TD (CN024, BLK)
TO (CN023, BLK)
TS (CN022, RED)
Fig. 10-4
68
button.
Varistror (VA002)
Varistror (VA001)
Terminal plug (CN015, BLK)
EMG (CN014, BRN)
OC (CN013, BLU)
ROM (CN012, WHT)
IC007
PRY (CN110, YEL)
C2 (CN020, WHT)
C1 (CN021, WHT)