8. Maintenance

The components of the Vacumat Eco are largely maintenance-free.
Nevertheless, it is recommended to perform an annual visual check of the system (including for leaks). In addition, the dirt trap to be provided
by the customer in the inflow line must be cleaned at least once a year, even if automatic detection does not require this. Cleaning may also be
done at more frequent intervals (depending on how dirty the system water is).
Should a visual check of the system necessitate further maintenance, this may also only be done by qualified personnel.
The temperature contact sensor must be visually inspected (Check assembly) at least during maintenance!
(already described in Commissioning)
It is also recommended to perform the vacuum test after maintenance.
The menu item Service in the Service menu can be used to read off the next service date. This should be an aid for the Operator.
The next service date (in brackets) is saved here. If the system clock is correctly set, the Operator will be informed about reaching
the date via a message.
365 days for maintenance 1 and 548 days (1.5 years) for maintenance 2 are provided after commissioning.
The Vacumat Eco continues to work when a group error message is triggered.
"Service done" should only be confirmed by authorised staff. The control unit then determines the next service date itself.
Maintenance 1 stands for maintenance device.
Maintenance 2 stands for the periodic inspection of electrical equipment.
8.1

Malfunction list / error messages

Error no.
Error message
Error / Name
PS 20mA ↑
2
Pressure sensor overcurrent /
sensor fault
PS 4mA ↓
3
Pressure sensor cable break /
sensor fault
VS 20mA ↑
4
Vacuum sensor overcurrent /
sensor fault
VS 4mA ↓
5
Vacuum sensor cable break /
sensor fault
↓↓ Temp
6
Temperature sensor short circuit /
sensor fault
↑↑ Temp
7
Temperature sensor cable break /
sensor fault
↓ Pressure
8
Lower alarm limit pressure
undershot (Pa min)
↑ Pressure
9
Upper alarm limit pressure
exceeded (Pa max)
↓ Temp
12
Temperature range undershot
↑ Temp
13
Temperature range exceeded
14
TC / FC motor
TC / FC message motor pump
15
Dry running
Filling level limit in the vessel
permanently undershot
22
Top-up volume
IWZ (pulse water meter) delivers no
water after top-up request
Effect / Action
System in forced rest; motor, motor ball valve
immediately Off / Reduce pressure in system /
change sensor.
System in forced idle mode; motor, motor ball
valve immediately Off / Repair cable / change
sensor.
System in forced idle mode; motor, motor
ball valve immediately Off / Reduce pressure /
change sensor.
System in forced idle mode; motor, motor ball
valve immediately Off / Repair cable / change
sensor.
Fault shutdown / Check cable and clamping /
change sensor.
Fault shutdown / repair cable / change sensor.
Fault shutdown / Lead pressure in the working
pressure range.
Fault shutdown / Lead pressure in the working
pressure range.
Fault shutdown / guide temperature to
operating temperature range.
Fault shutdown / guide temperature to
operating temperature range.
Fault shutdown.
System in forced idle mode; motor, motor ball
valve immediately Off / switch off, 5 min break,
switch on.
System in forced idle mode; motor, motor ball
valve immediately Off / expand supply line,
exclude pressure port contraction.
Top-up off / Ensure supply.
holding /
subject to mandatory
acknowledgement
NO
NO
NO
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
19