Electrical Wiring
(A) Definition and description of SW03
SW0 3_1
Address
setting mode
SW032
Code-
set indoor
SW038
unit address
and
centralized
controller
address
(Note2)
Note* :
Set the address by code when connecting the centralized controller or gateway or charge system.
Address of the centralized controller = communication address + 0 or + 64. SW03_ 2 = OFF, address of the centralized
controller = communication address + 0 = communication address SW03_ 2 = ON, address of the centralized controller =
communication address + 64 (applies when the centralized controller is used and there are more than 64 indoor units).
To use with 0010451181A in use, using code for address setting is required. Set SW03_1 = 0N and SW03_ 2 = OFF; SW03_3,
SW03_ 4, SW03_5, SW03_6, SW03_7, and SW03_ 8 are address codes that are set according to the actual address. The
address-setting function of the wired controller for ultrathin card machines is disenabled.
[1]
0
1
[2]
[3]
[4]
[5]
[6]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
...
...
...
...
...
0
1
1
1
1
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
...
...
...
...
...
1
1
1
1
1
Address setting mode
Automatic setting (default)
Code-set address
[7]
[8]
Address of
indoor unit
0
0
0# (Default)
0
1
1#
1
0
2#
...
...
1
1
63#
0
0
0#
0
1
1#
1
0
2#
...
...
1
1
63#
20
Address of
centralized
controller
0# (Default)
1#
2#
63#
64#
65#
66#
127#