Carrier 40VC009F-7S-QEE Manual De Instalación Y Propietario página 26

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 105
Electrical Wiring
(B) Definition and description ofSW03
SW03_1
Address setting mode
SW03_2
~
SW03_8
controller address
Note*:
• Set the address by code when connecting the centralized controller or gateway or chargesystem.
• Address of the centralized controller=communication address+0or +64.
• SW03_ 2=OFF, address of the centralized controller=communication address+0=communication address
• SW03_ 2=ON, address of the centralized controller=communication address+64 (applies when the centralized controller
is used and there are more than 64 indoor units).
• To use with 0010451181A in use, using code for address setting is required. SetSW03_1=0N
andSW03_2=OFF;SW03_3,SW03_4,SW03_5,SW03_6,SW03_7,andSW03_8are address codes that are set according
to the actualaddress.
• The address-setting function of the wired controller for ultrathin card machines isdisenabled.
[1]
0
1
[2]
0
0
Code-setindoor
0
unit address
...
andcentralized
0
(Note*)
1
1
1
...
1
Address setting mode
Automatic setting (default)
[3]
[4] [5]
[6]
[7]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
...
...
...
...
...
1
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
...
...
...
...
...
1
1
1
1
1
19
Code-set address
[8]
Address of
Address ofcentralized
indoor unit
controller
0
0# (Default)
0# (Default)
1
1#
1#
0
2#
2#
...
...
...
1
63#
63#
0
0#
64#
1
1#
65#
0
2#
66#
...
...
...
1
63#
127#

Publicidad

Tabla de contenido
loading

Tabla de contenido