INSTALLER
INSTALLER
- TYPE OF ACTUATION
Set the parameter in question to ITRF05/AKM (default value)
- TYPE OF HEAT REQUEST
This parameter allows you to specify the type of heat request, it is
possible to choose from among the following options:
THERMOSTAT (factory setting): the heat request is generated with an
ON/OFF thermostat
REC10 MASTER: the heat request is generated by the REC10
MASTER; in this case the REC10 assumes the function of MACHINE
INTERFACE
- TYPE OF ZONE
This parameter allows you to specify the type of zone to be heated, it
is possible to choose from among the following options:
HIGH TEMPERATURE (factory setting):
LOW TEMPERATURE
- MIN SET HEAT
This parameter allows you to specify the minimum heating setpoint that
is possible (range 20°C - 80.5°C, default 40°C for high temperature
systems - range 20°C - 45°C, default 20°C for low temperature
systems)
- MAX SET HEAT
This parameter allows you to specify the maximum heating setpoint that
is possible (range 20°C - 80.5°C, default 80.5°C for high temperature
systems - range 20°C - 45°C, default 45°C for low temperature
systems)
- CHANGING NAME
This parameter allows you to attribute a specific name to the heating zone
- POR
This parameter allows you to enable the central heating programming
timing for the zone concerned if the heat request is carried out using a
room thermostat
Time schedule not enabled = 0
When the room thermostat contact closes the heat request is always
met without any time band limitation
Time schedule enabled = 1
When the room thermostat contact closes the heat request is enabled
according to the programming timing.
Note: in this case make sure that the operating mode of the zone is set
to AUTO in the STATE menu.
5.2.3
Anti-legionella function (only if connected a water
tank with probe)
The machine has an automatic ANTI-LEGIONELLA function that, if
necessary, heats the domestic water to 65°C and keeps it at that temperature
for 30 minutes to prevent the proliferation of bacteria in the water tank. This
function can be set to be activated every day or every week.
This function is not performed if the water tank temperature has reached
65°C over the past 24 h - in case it is set to start daily - or over the last 7
days - in case it is set to start once a week.
If the function is activated, it is performed every day at 3:00 a.m. if set to
start every day, or on Wednesdays at 3:00 a.m. if set to start every week.
Once the function is in progress, it has top priority and cannot be interrupted.
b
The function is not performed when the boiler is OFF.
The function can be activated by accessing the TECHNICAL menu of
REC10:
- select MENU from REC main page and press CONFIRM
- access the technical parameters as explained in the section "4.1 Access
to the technical parameters"
- select ANTI-LEGIO using with the "up" and "down" keys, confirming
the selection
WEATHER COMPENSATION
THERMOREGULATION
RANGE RATED
CALIBRATION
COMBUSTION ANALYSIS
ANTI-LEGIONELLA
INSTALLER
INSTALLER
INSTALL
INSTALL
MAIN
MAIN
TECHNICAL
TECHNICAL
RANGE RATED
CALIBRATION
SWEEPER
ANTI-LEGIO
- select one of the options FUNCTION NOT ACTIVE, DAILY FUNCTION,
WEEKLY FUNCTION with the "up" and "down" keys, confirming the
selection
ANTI-LEGIONELLA
FUNCTION NOT ACTIVE
FUNCTION NOT ACTIVE
DAILY FUNCTION
DAILY FUNCTION
WEEKLY FUNCTION
WEEKLY FUNCTION
INSTALLER
INSTALLER
5.2.4
Time band schedule function (room thermostat)
It is possible to set a time schedule for heating function and for the water
tank filling (is installed) from the boiler.
Whenever the heating system is managed by a room thermostat, and
therefore without any time schedule, it is possible to tie the heat requests
coming from the device to programmable time bands by setting the
parameter POR = 1 (see section "5.2.2 Configuration of the zone" ), in other
cases it is always enabled.
To access this function:
- select MENU on the main page of the REC10 and press "ok"
FRI
MON
FRI
18/05/2013
MENU
MENU
INFO
INFO
HOT WATER TEMPERATURE
HOT WATER TEMPERATURE
- using the "up" and "down" keys select TIME SCHEDULE confirming
the selection
TIME SCHEDULE
TIME SCHEDULE
SELECT OPTION
From this menu it is possible to access the display and adjustment of the
time schedule for the heating functions of the zone rather than for the
domestic water tank. For each day of the week it is possible to set up to 4
bands, characterised by a starting time and an end time.
Note: for more details on the use of the programming timing see the USER
MANUAL of the REC10.
MON
MON
SCHEDULE
SCHEDULE
18/11/2013
MAIN
MAIN
SELECT THE ZONE
5.2.5
Setting the thermoregulation
Thermoregulation only works with the outdoor temperature sensor
connected and active only for the HEATING function; therefore, once
installed, connect the outdoor temperature sensor to the specific
connections on the boiler terminal board.
This enables the THERMOREGULATION function.
The temperature measured by the outdoor temperature sensor is displayed
on the initial page in the top right, alternating with the display of the time.
ANTI-LEGIO
PLANT
PLANT
12:17
STATE
1.3 bar
STATE
30
°C
.3
SET
SET
MENU
MENU
SETTINGS
SETTINGS
SELECT OPTION
MAIN
MAIN
12:17
START
END
START
END
07:30
08:30
11:30
13:30
18:00
22:30
ZONE SCHEDULE
ZONE SCHEDULE
ENGLISH
SELECT
SELECT A DAY
A DAY
THURSDAY
THURSDAY
17