Contactor Relay
Instructions
Limited protection against contact with live parts
Degree of protection IP 20 to IEC 60529
!
Safe from finger touch to DIN VDE 0106, Part 100
Commissioning and maintenance by qualified personnel only.
Follow the operating instructions.
WARNING:
HAZARDOUS VOLTAGE
CAN CAUSE ELECTRICAL SHOCK
DISCONNECT POWER BEFORE PROCEEDING
WITH ANY WORK ON THIS EQUIPMENT.
Installation
For dimension drawings (dimensions in mm) see
> Fig. I a
a.c. operated
> Fig. I b
d.c. operated
Minimum clearances from earthed parts: 8 mm
Snap onto 35 mm standard mounting rail to DIN EN 50 022 or fix on a
plain surface with two M4 screws. With screw mounting, always use
plain washers and spring washers.
Cover the contactors during installation if foreign particles, such as
swarf, can fall onto them. Install contactors in a housing if they are
exposed to dirt, dust or aggressive atmospheres.
For permissible mounting positions see
> Fig. II a
a.c. operated
> Fig. II b
d.c. operated
Installation
The terminal screws can be tightened with a power screwdriver.
Screwdriver blade width: 5 to 6 mm
Permissible conductor cross>sections :
Solid
Finely stranded with end sleeve
AWG wires
Tightening torque standard type
Tightening torque auxiliary contact block 0.8 to 1.1 Nm/7 to 10 lb
Use 75 ∞C copper wire only.
For circuit diagram and position of connection terminals see Fig. III.
> Fig. III a
4NO
> Fig. III b
3NO+1NC
> Fig. III c
2NO+2NC
Operation
Observe operating voltage (see rating plate of magnet coil).
The operating state of the contactor is shown at the contact carrier; see
Fig. IV.
Maintenance
The following components can be replaced:
magnet coil, single>pole auxiliary contact block 3TX40.
For Order Nos. see Catalog NS K.
Only use of original spare parts ensures the operational safety of the
contactors.
2
AND BURNS.
2
2¥ 0.5 to 1 mm
2
2¥ 1 to 2.5 mm
2
1¥ 4 mm
2
2¥ 0.75 to 2.5 mm
2¥ AWG 18 to 12
0.8 to 1.4 Nm/7 to 12 lb
Order No.: 3ZX1012>0TH00>1AA2
Cleaning
Remove dust by suction.
Auxiliary contact block
For replacement see Fig. V.
Magnet coil
For coil replacement see
> Fig. VI a
a.c. coil
> Fig. VI b
d.c. coil
Ensure that the pole faces of the magnet coil are clean. Do not use grease
solvents or sharp objects for cleaning.
Technical Data
Permissible ambient temperature
> Operation
> Storage
Rated insulation voltage U i
Rated operating current
I e /AC>12/AC>1
Rated operating voltage
> 230 V
> 240 V
> 400 V
> 415 V
> 500 V
> 690 V
Rated operating voltage
> 24 V
> 48 V
> 110 V
> 220 V
> 440 V
> 600 V
Short>circuit protection:
> Fuse>links
NEOZED and DIAZED, gL (gG)
> Circuit>breaker, C>char.
Auxiliary contact block 3TX40
Rated operating current
I e /AC>12/AC>1
.
in
Rated operating voltage
.
in
> 230 V
> 400 V
> 500 V
> 690 V
Rated operating voltage
> 24 V
> 48 V
> 110 V
> 220 V
> 440 V
> 600 V
Short>circuit protection:
> Fuse>links
NEOZED and DIAZED, gL (gG)
> Circuit>breaker, C>char.
For further data and accessories see Catalog NS K.
3TH30
DIN VDE 0660, IEC 60947
> 25 to+55 ∞C
> 50 to+80 ∞C
AC 690 V
A
16
Rated operating
current I e /AC>15/AC>11
A
10
A
10
A
6
A
4
A
4
A
2
Rated operating
current I e /DC>13/DC>11
A
10
A
5
A
0.9
0.45
A
A
0.25
A
0.2
A
16
A
16
A
10
Rated operating
current I e /AC>15/AC>11
A
5.6
A
3.8
A
2.5
A
1.8
Rated operating
current I e /DC>13/DC>11
A
10
A
4.6
A
0.8
A
0.2
A
0.11
A
0.08
A
16
A
10