Regulatory Compliance and Safety Information Regulatory Compliance and Safety Information Cisco NCS 560 Series Routers
Statement 7003 Telcordia GR-1089 NEBS Standard
for Electromagnetic Compatibility and Safety
Warning
The intrabuilding port(s) of the equipment or subassembly must use shielded intrabuilding
cabling/wiring that is grounded at both ends.
Statement 7004 Special Accessories
To comply with emission and immunity requirements, shielded cable is required for connection to .
Statement 7005 Intrabuilding Lightning Surge and
AC Power Fault
Warning
The intrabuilding port(s) of the equipment or subassembly must not be metallically connected
to interfaces that connect to the outside plant (OSP) or its wiring. These interfaces are designed
for use as intrabuilding interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE)
and require isolation from the exposed OSP cabling. The addition of primary protectors is not
sufficient protection to connect these interfaces metallically to OSP wiring.
Statement 7012 Equipment Interfacing with AC
Power Ports
Warning
This equipment shall be connected to AC mains provided with a surge protective device (SPD)
at the service equipment complying with NFPA 70, the National Electrical Code (NEC).
Statement 7013 Equipment Bonding Networks
Common Bonding Network (CBN)
Note
This equipment is suitable for installations utilizing the insert CBN.
Regulatory Compliance and Safety Information - Regulatory Compliance and Safety Information Cisco NCS 560 Series
Routers