Electrical Wiring - Sime Format.zip 30 OF S 25 Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
IT
ES
during installation:
– Insulate the exhaust pipe and install a
condensation collection system at the
PT
base of the vertical pipe.
– If the pipe passes through combustible
GB
walls, insulate the section of the flue pipe
passing through the wall with a 30 mm
GR
thick fibreglass pipe covering with a den-
sity of 50 kg/m
3
.
RO
In "BF TS" models this type of exhaust pipe is
installed using the special kit, code
RUS
8089904. For kit assembly instructions,
refer to point 2.9. 1 .
Protect the intake with the optional acces-
sory, code 8089501.
The accessory is assembled by cutting a 50
mm long segment from an ordinary ø 80
extension and inserting it on the air intake,
on which the accessory is then fitted, ancho-
red to the pipe segment with the screws pro-
vided (fig. 10).
Kit code 8089904
intake diaphragm, which must be used as
shown in fig. 8/a, depending on the maxi-
mum permitted flow.
Maximum flow resistance must be no
more than 7.6 mm H
- 9 mm H
O in vers. "30 BF TS" - 12 mm
2
H
O in vers. "35 BF TS".
2
As the maximum pipe length is determined
by adding up the flow resistance of the
various individual accessories installed, refer
to Table 1 for calculation.
2. 1 0
POSITIONING OF OUTLET
TERMINALS
The outlet terminals for forced draught
TABLE 2
Siting of terminal
A - below openable window
B - below ventilation opening
C - below eaves
D - below balcony (1)
E - from adjacent window
F - from adjacent ventilation opening
G - from horizontal or vertical soil or drain pipes (2)
H - from corner of building
I - from recess in building
L - from ground level or other treadable surface
M - between two terminals set vertically
N - between two terminals set horizontally
O - from a surface facing without
openings or terminals
P - as above but with openings and terminals
1) Terminals below a practicable balcony must be located in such a way
that the total path of the smoke from its outlet point from the termi-
nal to its outlet point from the external perimeter of the balcony,
including the height of possible railings, is not less than 2000 mm.
2) When siting terminals, where materials that may be subject to the
action of the combustion products are present in the vicinity, e.g.,
eaves, gutters and downspouts painted or made of plastic mate-
rial, projecting timberwork, etc., distances of not less than 1500
mm must be adopted, unless adequate shielding is provided to
guard these materials.
78
is supplied with the
O in vers. "25 BF TS"
2
systems may be located on the outer walls
of the building. Table 2 shows approximate,
non-binding minimum distances to be met
for a building of the type shown in fig. 11.
2. 1 1
If you must replace the electric power
cable supplied with the boiler, order it exclu-
sively from Sime.
The power supply must be single-phase
230V - 50 Hz through a main switch pro-
Appliances from 7 to 35 kW
(distances in mm)

ELECTRICAL WIRING

600
600
300
300
400
600
300
300
300
2500
1500
1000
2000
3000
cod. 8089501
tected by a fuse with a distance of at least
3 mm between contacts.
NOTE: The boiler must be con-
nected with an efficient groun-
ding system. SIME shall not be
held liable for injury or damage resulting
from failure to ground the boiler.
2. 1 1. 1
Electrical panel (fig. 12)
Before performing any kind of operation,
Fig. 10
Fig. 11

Publicidad

Tabla de contenido
loading

Tabla de contenido