Messages In The Display - Conergy IPG T Serie Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 126
8 Help in the case of faults
Fault indicator
TEMP HIGH
TEMP LOW
TEMP CRITICAL
58
LED is off
The status of this LED indicator has no signifi-
cance for the information currently displayed.
8.2

Messages in the display

If a fault occurs in the inverter, the current fault indicator will
be shown in the display. The top line shows the numeric code
of the fault, and the second line gives a fault indicator. The
faults listed cause the inverter to switch off. It normally
switches back on automatically once the fault has been
cleared. If the inverter does not switch back on or you cannot
clear the fault, Contact the manufacturer's service centre
(contact information on the back of the manual).
Possible cause
| Ambient temperature is
too high
| Ambient temperature is
too low,
T < -20 °C
| Temperature in the de-
vice is too high
| Electronics fault
| Fan fault
Operating manual
Possible fault rectification
The inverter requires cool ambi-
ent air
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
| Test the fans (see chapter 7.2,
page 47)
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
| Check the installation condi-
tions (see chapter 4.2.1,
page 22)
| Test the fan (see chapter 7.2,
page 47)
| If the fault continues, Contact
the manufacturer's service
centre (contact information on
the back of the manual).
Conergy IPG T series

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ipg 8 tIpg 11 tIpg 15 t

Tabla de contenido