Commissioning

Temperature test
Conergy SmartControl System
After you have connected the hardware components and
switched on the power supply, Conergy recommends that
you check that each hardware component is functioning
correctly. Only after all of the function tests have been carried
out successfully are the hardware components of the
Conergy SmartControl System functional. Installation is not
complete until a successful function test has been
performed.
7.1

ET sensor function test

When all the connections of the ET sensor are correctly
connected and the power supply is switched on, voltage is
supplied to the sensor inputs of the Conergy SmartControl.
These voltage values are directly proportional to the
measured variables of the ET sensor. Installation is not
considered complete until these voltage measurements
deliver reasonable results.
Voltage between the
connections
Temp and GND_Sens
LUM and GND_Sens
The voltage between the connections Temp and GND_Sens
is in direct proportion to the temperature measured by the ET
sensor.
Measure voltage
1. Measure the voltage U
and GND_Sens.
2. Calculate the temperature.
ϑ = 100 x U
Operating manual
Variable to test
Temperatureϑ
Irradiation
between the connections Temp
Temp
- 125
Temp
7 Commissioning
RR
61