7 Commissioning
Example
62
U
= 1.35 V
Temp
ϑ = 100 x 1.35 - 125
ϑ = 10 °C
3. Estimate whether the temperature value is realistic (in the
example, ϑ = 10 °C). Only once this is the case, is the ET
sensor correctly connected.
Note that the temperature values refer to the temperature at
the module level.
The following diagram illustrates the relationship between
voltage and temperature.
Fig. 7-1: Voltage characteristic of the temperature sensor
Operating manual
Temperature ϑ [°C]
Conergy SmartControl System