For your safety
Read all instructions and mounting steps carefully.
Keep the instructions for maintenance or disassembly
work.
Explanation of the warning levels
Observe and follow the warnings.
Non-observance of the warnings may lead to injuries or
material damage!
WARNING! Indicates dangers which can
result in serious and/or fatal injuries.
CAUTION! Indicates dangers which can result
in injuries or health hazards.
NOTICE. Indicates dangers which
can result in material damage or malfunc-
tions.
TIP. Indicates information containing advice
or a useful note.
Explanation of important symbols and
pictograms
Indicates professional personnel who are
trained and authorised to carry out the elec-
trical connection.
Indicates professional personnel who are
trained and authorised to carry out the
mounting.
Safety notes
WARNING! Risk of electric shock!
Never work with voltage applied.
6 | 36
10258341 | 211217 | © trilux.com
LIVELINK LAN DR
LIVELINK LAN DR
Important information on electronic control gear
units (ECG)
A neutral conductor interruption in the three-phase
circuit leads to overvoltage damage in the lighting sys-
tem. Only open the neutral conductor isolating terminal
in de-energised state, and close the neutral conductor
isolating terminal before switching on again. Do not
exceed the maximum permissible ambient temperature
t
of the luminaire.
a
Exceeding this limit reduces the service life and in
extreme cases there is a risk of premature failure of the
luminaire. Design connection cables for the control
inputs of DALI control gear (1-10 V, DALI etc.) to be 230
V mains voltage-proof (basic insulation).
Important notes on control units
• Do not exceed the maximum permissible ambient
temperature ta of the control unit. Exceeding this
limit reduces the service life, and in extreme cases
there is a risk of premature failure of the control
unit.
• Lay out the connection cables for the control inputs
of DALI control gear 230 V mains voltage-proof
(basic insulation).
• A maximum of 64 DALI loads per DALI bus are
permitted.
• A maximum of 10 gateways can be connected in
series.
Important notes for checking the installation
Check the installation before commissioning. To
check the installation the gateway features a function
for the broadcast identification of all connected de-
vices.
• Short key press (Test key): all devices flash
• Press the key again (Test key): all devices stop
flashing
• Key press for 10 s (Reset key): Gatway is reset to
factory settings