Remark:
* A disconnect switch should be required. Check the local code.
** Use a ring tongue terminal in order to connect a ground wire to terminal.
INDOOR UNIT A
Terminal block
208/230 V AC
1phase 60 Hz
Terminal block
UNIT A
CONNECTING WIRES AND CONNECTING GROUND WIRE
• Use solid conductor AWG14 or stranded conductor AWG14.
• Use double insulated copper wire with 600 V insulation.
* Follow local electrical code.
POWER SUPPLY CABLE AND GROUND WIRE
• Use solid or stranded conductor AWG14.
* Follow local electrical code.
WARNING:
For future servicing, give extra length to the connecting wires.