Regulator pressure gauge
The current line pressure is displayed on the regulator pressure
gauge. This pressure can be adjusted by rotating the pressure
regulator knob.
Safety valve
This valve is designed to prevent system failures by relieving
pressure from the system when the compressed air reaches a
predetermined level. The valve is preset by the manufacturer and
must not be modified in any way. To verify the valve is working
properly, pull on the ring. Air pressure should escape. When the
ring is released, it will reset.
Tank pressure gauge
The tank pressure gauge indicates the pressure of the air in the
tank.
Drain valve
The drain valve is used to remove moisture from the air tank after
the air compressor is shut off.
Motor thermal overload protector
This air compressor is equipped with a thermal overload device
which will turn the air compressor off automatically, if the air
compressor becomes overheated. If the motor turns OFF
repeatedly, check for the following possible causes first: Low
Voltage from the outlet. Lack of proper ventilation or outside air
or room temperature too high. Extension cord too long or wrong
gauge wire used.
To reset the air compressor:
Turn the air compressor off.
Unplug the air compressor, and allow it to cool for 30 minutes.
Plug the air compressor into an approved outlet.
Turn the air compressor on.
Air filter intake
This filter is designed to clean air coming into the pump and
requires no maintenance when operated in accordance with the
warnings and operating instruction outlined in this manual. To
ensure the pump continually receives clean, cool, dry air do not
operate this compressor in dust filled atmosphere. Ventilation
openings must be kept free from obstructions.
ATTACHING HOSE
Insert the hose into the quick coupler already installed on the
compressor (see fig. 3).
WARNING
Do not attach any tools to the open end of
the hose until start-up has been completed.
Firmly grasp the open end of the hose; hold facing away from
yourself and others.
BREAKING IN THE PUMP
See figures 3 - 4.
Check and tighten all bolts, fittings, etc.
Turn the pressure regulator knob fully clockwise to open the
air flow. Turn the locking nut clockwise to lock.
Place the switch in the OFF (O) position and plug in the power
cord.
Open the drain valves completely.
Turn the air compress ON ( l ) and run the air compressor for
10 minutes to break in pump parts.
Place the switch in the OFF (O) position.
Close the drain valves.
Allow the unit to cool for 30 minutes.
Pressure
regulator
knob
Quick
couplers
9
Locking
nut
On/Off
switch
Fig. 3
Drain valve
Drain valve
Fig. 4