Installing Two Exterior Hoods; Connecting The Drain - Broan ERV140TE Guia De Instalacion

Ocultar thumbs Ver también para ERV140TE:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

3. INSTALLATION (
CONT
3.8 I
T
E
NSTALLING
WO
XTERIOR
Choose an appropriate location to install the exterior hoods:
• There must be a minimum distance of 6 feet (1.8 m)
between the hoods to avoid cross-contamination
• There must be a minimum distance of 18 inches
(457 mm) from the ground
WARNING
!
Make sure the intake hood is at least 6 feet (1.8 m)
away from any of the following:
• Dryer exhaust, high efficiency furnace vent,
central vacuum vent
• Gas meter exhaust, gas barbecue-grill
• Any exhaust from a combustion source
• Garbage bin and any other source of contamination
Refer to figure at right for connecting insulated ducts to the
exterior hoods. An "Anti-gust intake hood'' should be installed
in regions where a lot of snow is expected to fall.
3.9 C
D
ONNECTING THE
RAIN
A drain tubing (included) must be installed for model HRV150TE. For model ERV140TE, it is not required, however, it
is recommended for climates where the outside temperature typically remains below -13°F (-25°C), (over a 24-hour
period) for several days in a row, combined with an indoor humidity of 40% or higher.
16"
(406 mm)
VO0176A
Cut 2 sections of the plastic tube, at least 16" (406 mm) long, and
attach them to each inner drain fitting, located under the unit.
Join both short sections to the "T" junction and main tube as shown.
VD0239
NOTE: For model ERV140TE, remove both drain plugs inside the
unit prior to install tubing.
'
)
D
H
OODS
16"
(406 mm)
D
RAIN PLUGS
E
XHAUST HOOD
I
NTAKE HOOD
18"
(457
)
MM
6'
(1.8
)
M
VD0028
CAUTION
Make a water trap loop in the tube to prevent the unit from
drawing unpleasant odors from the drain source. Make sure this
loop is located OVER the "T" as shown. Run the tube to the floor
drain or to an alternative drain pipe or pail.
IMPORTANT
If using a pail to collect water, locate the tube end approximately
1" from the top of the pail in order to prevent water from being
drawn back up into the unit.
11
6" Ø
(152
)
MM
O
PTIONAL DUCT
18"
(457
)
MM
T
APE AND DUCT TIE
T
IE WRAP
± 1"
VD0232A
LOCATION
6'
(1.8
)
M
18"
(457
)
MM