Quick Guide
1
1
Number Description
88
LCP data not compatible
89
Parameter read only
90
Parameter database busy
91
Parameter value is not valid in
this mode
92
Parameter value exceeds the
minimum/maximum limits
nw run
Not while running
Err.
A wrong password was
entered
1) These faults are caused by mains distortions. Install a Danfoss line filter to rectify this problem.
Table 1.6 Warnings and Alarms Code List
22
®
VLT
Micro Drive FC 51
Warnin
Alarm
Trip
Error
g
Lock
X
X
X
X
X
X
X
Danfoss A/S © 10/2017 All rights reserved.
Cause of problem
Occurs when copying from LCP if data are moved between
frequency converters with major differences in software
versions.
Occurs when trying to write to a read-only parameter.
LCP and RS485 connection are trying to update parameters
simultaneously.
Occurs when trying to write an illegal value to a parameter.
Occurs when trying to set a value outside the range.
Parameters can only be changed when the motor is stopped.
Occurs when using a wrong password for changing a
password-protected parameter.
MG02BC4P