5.1 Programming Mode Parameter List
Alarm Off Delay Time Parameter ( Default = 0)
It can be adjusted from 0 to 99 minutes.
When this parameter is 99, if increment button is pressed,
and alarm latching output is selected. To make the alarm latching output
passive, decrement button must be pressed in main operation screen.
Alarm Delay Parameter After Power On ( Default = 0)
This parameter defines the delay for the alarm is being active after power on.
It can be adjusted from 0 to 99 minutes.
Programming Mode Acessing Password ( Default = 0)
Password for entering to the programming mode is defined with this
parameter.It can be adjusted from 0 to 9999. ıf it is 0, programming mode is
accessed without entering password.
i
,
device with alarm output.
i
If no operation is performed in Programming mode for 20 seconds, device turns to
main operation screen automatically.
5.2 Operation Graphics of Alarm Output and Alarm Types
Power
Alarm
Status
Alarm
Output
Active
Led
Alarm
Output
Process High Alarm
Alarm
Output
ON
OFF
i
= Alarm Set Value
All manuals and user guides at all-guides.com
,
,
,
Power
Time
Alarm
Status
Time
Alarm
Output
Active
Led
Time
Alarm
Output
Time
Process Low Alarm
Alarm
Output
ON
OFF
Process Value
parameters are active in
=
( Alarm latching output is selected )
is observed
Time
Time
Decrement
button must be
pressed to make
alarm output
is passive
Time
Time
Process Value
9