REPLACEMENT OF THE POWER CORD
DO NOT TAMPER WITH THE
POWER CORD.
If the power supply cable is dam-
ATTENTION
aged, it must be replaced by the
manufacturer or the technical as-
sistance service or in any case
by a person with similar qualifi-
cations, in order to prevent any
risk.
The cable must be replaced in compliance with the laws in
force in the country where the product is used.
Replace the damaged power cord with a new one with the
same or equivalent characteristics to the original cord.
8.
REQUIREMENTS FOR THE
OPERATION, SERVICE AND
INSTALLATION OF APPLIANCES THAT
USE FLAMMABLE REFRIGERANT
GASES ACCORDING TO ANNEX DD OF
EN 60335-2-40
8.1
GENERAL WARNINGS
Any maintenance operation must
be performed by qualified per-
sonnel in accordance with the in-
OBLIGATION
structions in this manual.
Do not use any means to accel-
erate the defrosting or cleaning
process, other than those recom-
OBLIGATION
mended by the manufacturer.
The unit must be placed in a
room that does not have continu-
ous ignition sources (e.g. naked
OBLIGATION
flames, a gas appliance or elec-
tric heater in operation).
OBLIGATION
OBLIGATION
OBLIGATION
R290
R290
8.2
FIRE RISK
cod. 3541T580 - Rev. 06 - 04/2022
Do not pierce or burn.
Remember that refrigerant fluids
may be odorless.
The appliance must be installed,
operated and placed in an instal-
lation space with an area greater
than 10 m
and a minimum height
2
of not less than 2 meters. The
overall volume of the installation
compartment must be greater
than 20 m
.
3
The air inlet and outlet of the ap-
pliance must be channelled to
the external environment as in-
dicated in paragraph 6.6 on page
136.
The product is supplied with an
R290 refrigerant charge of 0.15
kg; any recharging operations
can only be performed at the
manufacturer's production site.
No repairs/replacements are al-
lowed on components that are
an integral part of the refrigerant
circuit.
The product must be installed in
a room equipped with adequate
air change to prevent the risk of
fire in case of a refrigerant gas
leak.
If the above is not possible, the
installer must carry out the nec-
essary work to ensure that no re-
frigerant gas stagnation occurs.
EN
149