TFQ 2 W
Normal/Reduced mode: Automatic
switching between normal and reduced
modes according to the timer program-
ming.
Note: In the reduced mode, the feed or
room reduction temperature set with
the knob (h) on the TFQ 2 W remote
control is effective.
5.2
Knobs (g) and (h)
With these knobs, the values set on the
TA... regulator for the feed temperature can
be corrected or the room temperature set for
normal operation (g) or reduced operation
(h) (see Section 5.3.1 for temperature ran-
ges).
5.3.1
Temperature Ranges
-Knob (g)
in Position
Left stop
Middle position
Right stop
Note: * A prerequisite is a correctly adjusted heating curve on the TA... regulator so that with-
out room temperature sensing, approximately 20 °C room temperature will be achieved.
Operational mode switch (f) in Position
Continuous
Normal mode
Normal mode
Feed Temperature Change
–25 K
0 K
+25 K
5.3
Switches (o) and (p)
When the top part of the remote control (a) is
removed from the base (b), the two switched
(o) and (p) are accessible on the back side
of the top part ( ).
With these switches, operation with or with-
out room temperature sensing is selected for
normal and reduced mode.
o Switch for normal mode
p Switch for reduced mode
❍ Operation without room temperature sen-
sing
● Operation with room temperature sensing
Switch (o) in Position
or
Continuous
Normal mode
Approx. Room Temperature *
–25 K
17 °C
0 K
20 °C
+25 K
23 °C
6
or
Normal mode
17 °C
20 °C
23 °C
GB