Luminous intensity distribution (Fig� 3�9/3�10/3�11/3�12)
Reach (SC only) (Fig� 3�13)
Note: If lights are mounted too close together, switching errors may occur as
the high-frequency signals emitted will interfere with each other. (Fig� 3�14 A)
The following measures will help to avoid switching errors of this kind:
• Allow a distance of at least 5 m between lights.
• Interconnect lights via the Smart Remote app and selectively deactivate the
sensor in individual lights via the Sensor-Off function (Fig� 3�14 B + C). As
a result of interconnection, movement will also switch lights ON in spite of
their sensor being deactivated.
4� Electrical connection
Wiring diagram (Fig� 4�1)
The mains supply lead is a 2 to 3-core cable:
L
= phase conductor (usually black or brown)
N = neutral conductor (usually blue)
PE = protective-earth conductor (green/yellow)
If you are in any doubt, identify the conductors using a voltage tester; then
disconnect from the power supply again. Connect phase (L) and neutral con-
ductor (N) to the terminal. Insulate protective-earth conductor (PE) and place it
next to terminal block.
For GL 80 SC/C, the protective-earth conductor must be connected to the
earth terminal (PE).
Important: Incorrectly wired connections will produce a short circuit later on
in the product or your fuse box. In this case, you must identify the individual ca-
bles and re-connect them. A mains power switch for turning the light ON and
OFF may of course be installed in the mains supply lead.
Important: The light source of this luminaire cannot be replaced. If the light
source needs to be replaced (e.g. at the end of its service life), the complete
luminaire must be replaced.
- 35 -