If using Push-to-Pair, then if the room has only this one room controller, or if the room controller was the primary in a network
with more than one room controller, then following the standard Push-to-Pair method will return the LMRC-611MCC to the previous
Network ID, since it is based on that Mac address of the room controller. But, if the room controller was not the primary, then you
must follow the procedure for adding a new device to an existing room, with this room controller as the new device.
The wrong lights and plug
loads are controlled
LEDs on the room controller
turn ON and OFF but load
doesn't switch
Lamps do not dim, or lamps
drop out at low dim levels
FCC REGULATORY STATEMENTS
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired
operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC
Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.
This equipment generates uses and can radiate radio frequency energy and, if not installed and used in accordance with the
instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be
determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the
following measures:
• Reorient or relocate the receiving antenna.
• Increase the separation between the equipment and receiver.
• Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
• Consult the dealer or an experienced radio/TV technician for help.
RF exposure warning
This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. At least 20 cm of separation
distance between this device and the user's body must be maintained at all times.
Any changes or modifications not expressly approved by The Watt Stopper Inc. could void the user's authority to operate the equipment.
IC Caution:
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions:
(1) This device may not cause interference, and
(2) This device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est
autorisée aux deux conditions suivantes:
(1) l'appareil ne doit pas produire de brouillage, et
(2) l'utilisateur de l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le
fonctionnement.
RF exposure warning
This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed
and operated with minimum distance 20cm between the radiator & your body.
Cet équipement est conforme aux limites d'exposition aux radiations de la IC définies pour un environnement non contrôlé. Cet
équipement doit être installé et utilisé à une distance minimale de 20 cm entre le radiateur et votre corps.
NOTE: No rights or licenses under patents owned or controlled by third parties, express or implied, are granted to use third-party
devices in combination with these products in a wireless mesh network, or to use third-party services to access, monitor or
control these products in a wireless mesh network via the internet or another external wide area network. Separate license rights
may need to be obtained from such third parties for such devices, combinations and services.
TROUBLESHOOTING
Configure the switch buttons and sensors to control the desired loads using the Push n' Learn
adjustment procedure or DLM Config App.
1. Make sure the DLM local network is not in PnL.
2. Check load connections to room controllers and/or plug load controllers.
1. Make sure a 0–10V dimming ballast and rapid start sockets are installed per the ballast
manufacturer's recommendation. Shunted sockets are typically not acceptable.
2. Disconnect the 0-10V wires from the RC then-short and open the 0-10V connection to
confirm the lights go full dim, full bright.
3. Check wiring per ballast manufacturer's instructions.
6