Configuration
Both DIP switches set to ON
This configuration activates the programming mode of the STO90,
indicated by "Config" on the HMI
One DIP switch set to ON and the other to OFF
This is not a valid configuration and the programming will not be
performed
Both DIP switches set to OFF
This configuration disables the programming mode of STO90
NOTE!
The DIP switches S2 must only be set to the ON position when CFW900 is in
the STO state. Attempting to enter the programming mode from any other state
different from the STO state will result in the fault F160.
Table 2.6: DIP switches S2
Description
Installation
CFW900 | 17