11. SOUND DATA
The noise level of units is basically due to the fan rotation speed.
Obviously, with the same air flow rate, the fan speed will be lower if the required static pressure is low, while it will be higher (and
therefore noisier) if the required static pressure is higher.
11.1 Noise levels
The table below shows the sound levels of the units at the nominal working conditions:
Nominal
E.S.P.
air flow
Ret. | Supp.
MOD.
Pa
m
/h
3
045
4500
200 | 250
060
6000
200 | 250
080
8000
200 | 250
100
10000
200 | 250
130
13000
200 | 250
Lw: sound power level calculated in accordance with EN 3744
Lp: sound pressure level measured in free field at 1 m from the unit, directionality factor Q=2, according to EN 3744 with ducted unit.
11.2 Sound attenuators reduction
The sound attenuators are of sound-absorbing baffles type. They are suitable for reducing the noise that propagates through the
ventilation systems in the aeraulic ducts.
To check the sound absorpion data to the various octave band frequencies, please refer to the our selection
software.
The sound attenuators are supplied in a dedicated section external to the base unit, thus increasing the total length of the unit
(depth and height of the section remain the same as the base unit).
Below are the additional section lengths according to size and profile, to be taken into account when calculating the final
length of the unit.
Additional dimensions sound attenuator section
045
MOD.
1000
Length
[mm]
Additional dimensions sound attenuator section
045
MOD.
Length
1020
[mm]
Octave band (Hz)
63
125
250
500
dB
dB
dB
dB
64
66
54
59
68
64
50
55
57
52
56
64
74
70
56
61
71
67
53
58
(50 mm profile)
060
1000
(60 mm profile)
060
1020
1K
2K
4K
dB
dB
dB
61
51
30
56
45
24
68
59
37
61
50
29
59
48
27
080
100
1000
1000
080
100
1020
1020
EN
Lw
Lp
8K
dB(A)
dB(A)
dB
69
51
22
69
51
18
71
51
29
76
56
21
73
54
21
130
1000
130
1020
24