13.7 Hydronic connections
All connections should be made with the best available current workmanship practice according to the indicated dimensions
of inlet and outlet diameters.
Outlet connections should be complete with water traps and their height calculated on the basis of the maximum negative
pressure existing at the drainage point. A semplified method is to assume this value equal to the total fan pressure and calcu-
late trap dimension as indicated in the picture below.
S1 = Ht / 10 + 35
S1 - S2 = minimum height, mm, as indicated
Ht = total fan pressure, Pa, as indicated in the "TECHNICAL SCHEDULE"
The lack of a siphon may affect the proper operation of the unit.
It is advisable to provide a siphon for EVERY SINGLE DRAIN. We also recommend that separated drains are NOT
connected with each other, before or after the siphon/s, but are left independent.
13.8 Hydraulic connection to the exchange coils
13.8.1 Water coils
The following requirements for water connections are also applicable for coils with other fluid, such as glicole solutions, dia-
thermal oil, etc. The following minimal requirements are recommended for any type of installations.
a) Provide appropriate supports for external circuit and thermal expansion joints with vibration isolators; avoid to load coil
connections.
b) Position water pipes and water circuit devices not to impede coil slide out, inspection panel openings and access to any
unit sections.
c) Avoid damages to coil connection solderings by fastening mechanical connections with care without applying any torsions
to the same especially when the exchangers are small.
EN
S1
S2
S2 = Ht / 10 x 0,75
33