WARNINGS:
• TO AVOID FIRE, SHOCK, OR DEATH, DISCONNECT POWER to all related circuits from
power distribution system (or service) of building before installing or servicing product!
• TO AVOID OVERHEATING, DO NOT install current transformer ("CT") in an area of
breaker arc venting or in an area where it would block ventilation openings.
• Power must be de-energized and the circuit opened in order to slip the CT over the
power line.
• Secure CT and route conductors so that they do not directly contact live terminals or bus.
• To be installed and/or used in accordance with appropriate electrical codes and regulations.
• If you are unsure about any part of these instructions, consult an electrician.
Description
Leviton solid core current transformers (CTs) are accurate, cost effective and less
susceptible to damage during installation. Solid core CTs slip over power lines to measure
the electrical current flowing through the line. The CT "secondary" wires connect to the
meter, facilitating power and energy calculations.
NOTE: For complete installation instructions specific to the meter being installed, please
refer to the meter installation guide.
Installation
WARNING: TO AVOID FIRE, SHOCK, OR DEATH; DISCONNECT POWER to all related
circuits from power distribution system (or service) of building before installing or servicing
current transformers!
1. Disconnect the conductor to be measured.
2. Insert the conductor through the center of the current transformer (CT). Verify the CT
orientation for Line / Load is correct using markings on CT.
NOTE: Ensure that the maximum current of the conductor does not exceed the
CT's rating.
3. Repeat Steps 1 and 2 if you are using more than one CT.
4. Connect the white wire on the CT to the positive terminal (+) on the measuring device.
5. Connect the colored wire (black, blue, red) on the CT to the negative (-) terminal on the
measuring device.
6. Reconnect the conductor and restore power.
7. You are now ready to begin your monitoring session.
Wiring Diagram
Schéma de câblage
Diagrama de Cableado
LINE / LIGNE / LÍNEA
N
L1
L2
L3
X1
White / Blanc / Blanco
Black / Noir / Negro
X2
White / Blanc / Blanco
X1
Black / Noir / Negro
X2
White / Blanc / Blanco
X1
Black / Noir / Negro
X2
LOAD / CHARGE / CARGA
FOR CANADA ONLY
For warranty information and/or product returns, residents of Canada should contact Leviton in writing at Leviton Manufacturing of Canada ULC to the
attention of the Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9 or by telephone at 1 800 405-5320.
Leviton warrants to the original consumer purchaser and not for the benefit of anyone else that this product at the time of its sale by Leviton is free of defects in materials and workmanship under normal and
proper use for five years from the purchase date. Leviton's only obligation is to correct such defects by repair or replacement, at its option. For details visit www.leviton.com or call 1-800-824-3005. This warranty
excludes and there is disclaimed liability for labor for removal of this product or reinstallation. This warranty is void if this product is installed improperly or in an improper environment, overloaded, misused,
opened, abused, or altered in any manner, or is not used under normal operating conditions or not in accordance with any labels or instructions. There are no other or implied warranties of any kind, including
merchantability and fitness for a particular purpose, but if any implied warranty is required by the applicable jurisdiction, the duration of any such implied warranty, including merchantability and fitness for a
particular purpose, is limited to five years. Leviton is not liable for incidental, indirect, special, or consequential damages, including without limitation, damage to, or loss of use of, any equipment,
lost sales or profits or delay or failure to perform this warranty obligation. The remedies provided herein are the exclusive remedies under this warranty, whether based on contract, tort or otherwise.
Solid Core Current Transformers
Cat. Nos. CDV01, CDV02
INSTALLATION INSTRUCTIONS
A
B
C
N
X1
A
X2
X1
B
X2
X1
C
X2
LIMITED 5 YEAR WARRANTY AND EXCLUSIONS
For Technical Assistance Call: 1-800-824-3005 (USA Only) or 1-800-405-5320 (Canada Only) www.leviton.com
CAUTIONS:
• CTs may not be installed in equipment where they exceed 75 percent of the wiring space of
any cross-sectional area within the equipment.
• Installation is intended for Overvoltage Category IV or Service Entrance.
• CTs are not suitable for Class 2 wiring methods and are not intended for connection to
Class 2 equipment.
• CT lead lengths may be extended up to 200 feet, although doing so may adversely affect
the accuracy of meter readings. When extending lead lengths, use twisted wires matching
the gauge of the CT's attached leads and follow NEC and local electrical codes.
• If this equipment is used in a manner not specified by Leviton, the protection provided by
the equipment may be impaired.
• For indoor use only.
Specifications
Operating ambient temperature rating
Relative humidity rating
Maximum Rated Voltage
Maximum Rated Current
100:333mV CTs
200:333mV CTs
Pollution Degree 2
Dimensions
Dimensions
Dimensiones
1.94 in.
49.30 mm
0.712 in.
18.10 mm
CDV01
0.59 in.
15 mm
1.771 in.
45 mm
0.078-0.157 in.
2-4 mm
0.374 in.
9.5 mm
1.574 in.
40 mm
2.283 in.
58 mm
CDV02
0.787 in.
20 mm
2.283 in.
58 mm
0.078-0.216 in.
2-5.5 mm
0.383 in.
9.75 mm
1.968 in.
50 mm
2.677 in.
68 mm
PK-A3308-10-02-5B
-30 to 55°C
90%
600V
Primary: 100A
Secondary: 0.333V +/- 0.2%
Primary: 200A
Secondary: 0.333V +/- 0.2%
Normally only non-conductive pollution occurs.
Occasionally, however, a temporary conductivity
caused by condensation must be expected.
0.762 in.
19.36 mm
-
+
144 in.
3657 mm
0.905 in.
23 mm
1.889 in.
P2
P1
48 mm
0.157 in.
4 mm
0.866 in.
22 mm
2.283 in.
P2
P1
58 mm
0.157 in.
4 mm
ENGLISH