BSP B/M/V _ _ _ - _ _ _ _ _ - _ _ _ A1A - S4(- _ _ _ )
Pressure Transmitter
Installation (continued)
Installation for connections per DIN 3852
Check before installation:
–
Does the sealing surface have a flawless surface?
–
Is any residue present?
–
Is the O-ring seated and in perfect condition in the
provided groove?
► Tighten the device by hand in the holding threads. Use
an appropriate open-end wrench to tighten and
observe the following tightening torques:
Torque 1/4"
Connec-
Connec tion
tion per
per
DIN 3852
DIN EN 837
approx.
approx.
5 Nm
20 Nm
Torque 1/2"
Connec-
Connec tion
tion per
per
DIN 3852
DIN EN 837
approx.
approx.
10 Nm
50 Nm
2
english
NPT
R-connec-
connec-
tion
tion
approx.
approx.
30 Nm
30 Nm
NPT
R-connec-
connec-
tion
tion
approx.
approx.
70 Nm
70 Nm
Electrical Connection
Only make the electrical connection with
pressure and power turned off.
Connect the device electrically according to the details on
the part label, the pin assignment table below and the
connection diagram.
Elec-
Standard version
trical
Transmitter
connec-
2-conductor,
3-conductor,
tions
current
voltage
output
output
Pin 1
Supply +
Supply +
Pin 2
n. c.
n. c.
Pin 3
Supply – /
Supply –
4...20 mA
(Out)
Pin 4
n. c.
0...10 V (Out)
Connection diagrams for standard version
Connection diagram for special version
Special
version
2-conductor,
current
output
Supply +
Supply – /
4...20 mA
(Out)
n. c.
n. c.