Descargar Imprimir esta página

SEELEY INTERNATIONAL Climate Wizard CW-H10 Manual De Instalación Y Funcionamiento página 45

Ocultar thumbs Ver también para Climate Wizard CW-H10:

Publicidad

APÉNDICE C
MODBUS REGISTERS
REGISTER
TYPE
9200
UINT
Commands
9201
UINT
Fan Speed
9202
Reserved
9203
Reserved
9204
Reserved
9205
UINT
Status
9206
UINT
Supply Fan Speed
9207
UINT
Salinity of Tank
9208
UINT
Chlorinator PWM
9209
UINT
Fault Code
9210
INT
Sensor 1 Temperature
9211
INT
Sensor 1 Relative Humidity
9212
INT
Sensor 2 Temperature
9213
INT
Sensor 2 Relative Humidity
COMMANDS
DESCRIPTION
Bit 3-15
0 - 1000
Bit 8 - 15
0 - 1000
0 - 6615
0 – 100
-400 to 700
-400 to 700
-400 to 700
-400 to 700
IEC Enable
DEC Enable
FS > 100
Off
VENT
NO Cooling
IEC & DEC
Enable
Drain
OPEN
Inlet Solenoid
OPEN
Low Probe
WET
High Probe
WET
Indirect Pump
RUNNING
Direct Pump
RUNNING
Drain
Close Drain
Open
Open Inlet
FAULT
Fault Code > 0
Fault Reset
No Fault
Fault
Present
Code 2
Bit 0
IEC Enable (Indirect Evaporative Cooling)
Bit 1
DEC Enable (Direct Evaporative Cooling)
Bit 2
Fault Reset
NOT USED
(0 to 100%) * 10
STATUS
Bit 0
FAULT
Bit 1
Low Probe WET
Bit 2
High Probe WET
Bit 3
Inlet Solenoid OPEN
Bit 4
Drain Valve OPEN
Bit 5
Indirect Pump RUNNING
Bit 6
Direct Pump RUNNING
Bit 7
Chlorinator RUNNING
NOT USED
Supply output percentage (0 – 100%) * 10
Salinity Level of the tank
0 – 100% Output of the chlorinator
If a fault is active the Fault Code number will be displayed. If multiple
faults are present, the fault codes will be cycled.
DEC Only
IEC Only
IEC & DEC
Cooling
Cooling
Cooling
ILL3748-A
IEC Pump
Water at
Water at
DEC Pump
Low Probe
High Probe
Run
ILL3749-A
Fault
Fault
Fault
No Fault
Present
Code 4
Reset
Present
CW-H
MANUAL DE INSTALACIÓN, FUNCIONAMIENTO Y MANTENIMIENTO 859749-G
DETAILS
Standby
ILL3748-A
DEC Pump
Only
ILL3749-A
ILL3750-A
|
45

Publicidad

loading

Este manual también es adecuado para:

Climate wizard cw-h15Climate wizard cw-h15sClimate wizard cw-h15s plus