93
Gen Over Volt Delay
94
Gen Over Freq Delay
95
Disconnect OP Delay (0-20.0)s
96
Timing Start
Timing Start Cir-cu-
97
late
98
Auto Start Inhibi-ted
Auto Start Circula-te
99
Inhibited
100
Over Power
101
Date
Custom Sensor
102
Curve
Note1: The default value in "No." column is for HGM420N and the number value needs to minus 5 for HGM410N.
Note1:
Note2: If "high temperature inhibit" is configured, or set auxiliary input as "inhibit high temperature stop" and this input is active, when
Note2:
temperature is higher than the preset value, or high temperature alarm input is active, controller will send warning signal only and not
stop the unit.
Note3: If "low oil pressure inhibit" is configured, or set auxiliary input as "inhibit low oil pressure stop" and this input is active, when
Note3:
oil pressure is lower than the preset value, or low oil pressure alarm input is active, controller will send warning signal only and not stop
the unit.
Note4:
Note4: If "low fuel level inhibit" is configured, or set auxiliary input as "inhibit low fuel level stop" and this input is active, when fuel
level is lower than the preset value, or low fuel level alarm input is active, controller will send warning signal only and not stop the unit.
Note5: Multiplex Input can be set as "auxiliary input" or "level sensor"; if one of them is set successfully, then the corresponding items
Note5:
are active. For instance, if set "Multiplex Input 3" as "Auxiliary Input", the related configuration items of auxiliary input 3 are active; if set
"Multiplex Input 3" as "Level Sensor", the related configuration items of level sensor are active;
Note6:
Note6: If default password (0318) isn't changed, it doesn't need to input when configuring parameters via PC software; if the password
is changed for the first time via PC software, it need to input password in password window.
Note7: Between input correct password and LCD back light haven't got dark, input parameter numbers can enter parameter setting
Note7:
interface when enters "Password Input" again.
Note8:
Note8: In teeth configuration interface, configure teeth status and power large than 20Hz, press start key for auto calculating teeth
numbers and press confirm key for changing teeth numbers.
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
(0-20.0)s
10.0
(0-20.0)s
2.0
0.0s
(0-1) (0-1)
0 0
(0-2) (
0
1-31)
1
(0-7)
0
(1-23)h
0
(1-59)min
0
(0-30000)min
30
(0-1)
0
(0-2)
0
(1-31)
1
(0-7)
0
(1-23)h
0
(1-59)min
0
(0-30000)min
30
(0-2)
0
(0-6000)kW
304
(0-6000)kW
290
(0-3600)s
5
Set the date of controller.
(0-3)
0
When generate voltage exceeds shutdown value
and last for a whi-le, gen over volt shutdown is
acti-ve.
When generate frequence ex-ceeds shutdown
value and last for a while, gen over freq shutdown
is active.
When disconnect conditions include oil pressure
and engine oil pressu-re is higher than disconnect
oil pressure delay, the genset is re-garded as start
successfully and starter will dis-connect.
0: Disabled; 1:Enabled 0:No-load; 1:On-load
0: monthly; 1: weekly; 2:daily
Day(0:monthly is active)
Week(0:weekly is active)
Prohibit start time (h)
Prohibit start time (min)
Duration
0: Disabled; 1:Enabled
0: monthly; 1: weekly; 2:daily
Day(0:monthly is active)
Week(0:weekly is active)
Prohibit start time (h)
Prohibit start time (min)
Duration
0 Inactive; 1 Warn; 2 Alarm Shutdown
Over power setting value
Over power warn return
Over power delay
When power is higher than preset value and du-
ration exceeds than delay, over power warning is
active. Return and delay value can be set.
0 Custom temperature sensor
1 Custom pressure sensor
2 Custom level sensor
3 Custom auxiliary sensor
Choose sensor which need to be set, input every
point(8 points need to be input) resistance and
corresponding value(or current, voltage) of curve.
11