1. PERFORMANCE AND CHARACTERISTICS
HGM400N series controller has two types:
HGM410N: ASM (Automatic Start Module), it controls generator to start/stop by remote signal;
HGM420N: AMF (Auto Mains Failure), updates based on HGM410N, moreover, has mains electric quantity monitoring and mains/genera-
tor automatic transfer control function, especially for automatic system composed by generator and mains.
2. SPECIFICATION
Items
Working Voltage
Overall Consumption
AC voltage Input:
3 Phase 4 Wire
3 Phase 3 Wire
Single phase 2 Wire
2 Phase 3 Wire
Alternator Frequency
Speed Sensor Voltage
Speed Sensor Frequency
Start Relay Output
Auxiliary Relay Output 1
Auxiliary Relay Output 2
Auxiliary Relay Output 3
Auxiliary Relay Output 4
Auxiliary Relay Output 5
Overall Dimensions
Panel Cutout
CT Secondary Current
Working Condition
Storage Condition
Protection Level
Insulation Intensity
Weight
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
Contents
DC8. 0V to 35. 0V, Continuous Power Supply.
<3W(Standby mode: ≤2W)
AC15V - AC360V (ph-N)
AC30V - AC620V (ph-ph)
AC15V - AC360V (ph-N)
AC15V - AC360V (ph-N)
50Hz/60 Hz
1.0V to 24V (RMS)
10,000 Hz (max)
5A DC28V power supply
5A DC28V power supply
5A DC28V power supply
5A DC28V power supply
5A AC250V voltage-free output
5A AC250V voltage-free output
126mm x 109mm x 44mm
110mm x 90mm
5A (rated)
Temperature: (-25~70)ºC;
Humidity: (20~90)%RH
Temperature: (-30~+80)ºC
IP55 Gasket
Object: among input/output/power supply
Quoted standard: IEC688-1992
Test method: AC2.2kV/1min
0.26kg
4
Ileak≤3mA