3. OPERATION
3.1 PUSHBUTTONS
Stop/ Reset
Start
Manual
Auto
Close/Open
Set/ Confirm
Up/Increase
Down/Decrease
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
Stop running generator in Auto/Manual mode;
In case of alarm condition, pressing the button will reset alarm;
In stop mode, pressing and holding the button for 3 seconds will
test indicator lights (lamp test);
During stopping process, press this button again to stop generator
immediately.
Start genset in Manual/Test mode. When press this key in starting
process, genset will skip to next status.
Pressing this key will set the module into manual mode.
Pressing this key will set the module into auto mode.
For close/open switch. Pressing this key can switch between
close/open interface and homepage. At close/open interface in
manual mode, pressing up/down keys can control open or close.
Pressing this key will enter into Main Menu;
In setting parameter status, press this key will shift cursor or con-
firm setting value.
Scrolls the screen up; shift the cursor up or increase the set value
in parameter setting menu.
When at close/open interface in manual mode:
Pressing this key can control mains close/open (HGM420N) and
gen close (HGM410N).
Scrolls the screen down; shift the cursor down or decrease the set
value in parameter setting menu.
When in close/open interface in manual mode:
Pressing this key can control mains close/open (HGM420N) and
gen close (HGM410N).