39
Over Current Delay
40
Fuel Pump On
41
Fuel Pump Off
42
Aux. Output 1
43
Aux. Output 2
43
Aux. Output 3
44
Aux. Output 3
45
Aux. Output 4
46
Aux. Output 5
47
Digital Input 1
48
Digital Input 1 Active
49
Digital Input 1 Delay
50
Digital Input 2
51
Digital Input 2 Active
52
Digital Input 2 Delay
53
Digital Input 3
54
Digital Input 3 Active
55
Digital Input 3 Delay
56
Digital Input 4
57
Digital Input 4 Active
58
Digital Input 4 Delay
59
Power On Mode
60
Module Address
61
Passwords
62
Crank Disconnect
Disconnect Magnetic
63
Pickup
Disconnect Magnetic
63
Pickup
64
Disconnect Gen Freq (10.0-30.0)Hz
65
Disconnect OP
High Temp. Inhibit
66
Enabled
Low OP Inhibit Ena-
67
-bled
Low Fuel Level
68
Inhibit
Config. Sensor
69
Inhibit
70
AC System
71
Temp. Sensor Curve
HGM410N/HGM420N GENSET
CONTROLLER USER MANUAL
(0-3600)s
30
(0-100)%
25
(0-100)%
80
(0-17)
14
(0-17)
2
(0-17)
5
(0-17)
3
(0-17)
5
(0-17)
6
(0-15)
1
(0-1)
0
(0-20.0)s
2.0
(0-15)
2
(0-1)
0
(0-20.0)s
2.0
(0-15)
10
(0-1)
0
(0-20.0)s
2.0
(0-15)
11
(0-1)
0
(0-20.0)s
2.0
(0-2)
0
(1-254)
1
(0-9999)
0318
(0-6)
2
(0-3000)r/min
360
(0-3000)r/min
360
14.0
(0-400)kPa
200
(0-1)
0
(0-1)
0
(0-1)
1
(0-1)
1
(0-3)
0
(0-12)
8
When load current has exceeded the set value and
the "over current" delay has expired, over current
alarm is initiated. When the set value is 0, only
warning and not to shutdown the generator.
When fuel level has fallen below the set value for
10s, "Fuel Pump On" alarm is initiated.
When fuel level has exceeded the set value for 10s,
"Fuel Pump Off" alarm is initiated.
Factory default: Fuel Relay Output
Factory default: Energized To Stop
Factory default: Gens closed
Factory default: Idle Control
Factory default: Close Generator
Factory default: Mains Closed
Factory default: High Temperature Input
Factory default: Close to active
Factory default: Low Oil Pressure Warning Input
Factory default: Close to active
Factory default: close
Factory default: Remote Start
Factory default: Close to active
Factory default: close
Factory default: Fuel Level Warn
Factory default: Close to active
Factory default: close
0: Stop Mode 1: Manual Mode 2: Auto Mode
Communication address of controller.
There are 3 conditions of disconnecting starter
with engine: Generator Frequency, Magnetic
Pickup, Oil Pressure. Each condition can be used
alone and simultaneously to separating the start
motor and genset as soon as possible. See 7.5
When engine speed higher than the set value, star-
ter will be disconnected.
When engine speed higher than the set value, star-
ter will be disconnected.
When generator frequency higher than the set
va-lue, starter will be disconnected.
When generator oil pressure higher than the set
value, starter will be disconnected.
Factory default: when high temperature occurs,
shutdown alarm is initiated. Note 2
Factory default: when low oil pressure occurs,
shu-tdown alarm is initiated. Note 3
Factory default: when low fuel level occurs, shu-t-
down alarm is initiated. Note 4
Factory default: when config. sensor value higher/
lower than the set value (particular case depends
on the sensor type), shutdown alarm is initiated.
0: 3P4W; 1: 2P3W 2: 1P2W; 3: 3P3W
SGX See 7.4
9