Descargar Imprimir esta página

engelmann HCA e2 Manual De Instrucciones página 29

Publicidad

Idiomas disponibles

Idiomas disponibles

conductor was
detected.
H 16 / Bit 4
Break of one of the
measuring sensors.
H 32 / Bit 5
Short circuit of one of
the measuring sensors.
H 64 / Bit 6
Reset by watch dog
timer.
H 128 / Bit 7
Remote sensor is
mounted.
13 Manufacturer
Engelmann Sensor GmbH
Rudolf-Diesel-Str. 24-28
69168 Wiesloch-Baiertal
Germany
Page 29 of 59
Article no.: 5081200002
No calculations are carried out. The
register for consumption is not being
updated.
No calculations are carried out. The
register for consumption is not being
updated.
The measured values and the time
since the last saving in the E
are lost (max. one hour). Calculations
are still being carried out.
No influence on the calculation.
Tel: +49 (0)6222-9800-0
Fax:+49 (0)6222-9800-50
E-Mail: info@engelmann.de
www.engelmann.de
2022_10_31
Defect on PCB board, high-
resistance NTC; defect of the
remote sensor in the remote
sensor operating mode
Defect on PCB board, low-
resistance NTC; defect of the
remote sensor in the remote
sensor operating mode
Undefined program status,
2
PROM
program sequence is not
within the specified time
cycle.
Remote sensor was mounted.
Subject to technical change! Errors excepted.