[125] Ethernet Test Transmission Cycle
Default (000000);
This value represents the interval between test transmissions, in minutes. Valid Range: 000000 - 999999. Once the unit has sent the ini-
tial periodic test transmission, all future test transmissions will be offset by the programmed number of minutes. See Sections [026 -
027].
Test Transmission Interval
NOTE: Minimum entry is 000005 (minutes). Programming an interval < 5 minutes will disable test transmission.
Communication Path Diagnostic
[901] Diagnostic Test Transmission
Default [OFF];
[1]
Ethernet 1.
[2]
Ethernet 2.
This Section may be used by the installer to force the module to send an immediate diagnostic test transmission to the receivers, to verify
that the communications path is available. If the test fails, an FTC Trouble is indicated.
System Information (Read Only)
NOTE: Sections [988] - [998] are provided for information (Read Only). Values can not be programmed in these Sections.
[988] DNS 1 IP Address
This Section will display the IP address of DNS Server 1. This is useful when the unit is configured for DHCP and you need to see the IP
address was assigned to the device by the DHCP Server. This value is programmed in Section [007] or created by DHCP .
[989] DNS 2 IP Address
This Section will display the IP address of DNS Server 2. This is useful when the unit is configured for DHCP and you need to see the IP
address that was assigned to the device by the DHCP Server. This value is programmed in Section [008] or created by DHCP .
[991] Firmware Version
This Section will display the current firmware version of the device. Update worksheets with new value after a firmware (flash) update is
completed.
[992] Ethernet IP Address
This Section will display the IP address of the Ethernet connection. This value is programmed in Section [001] or assigned by DHCP .
[993] Ethernet Gateway Address
This Section will display the IP address of the Ethernet Gateway. This value is programmed in Section [003] or assigned by DHCP .
[998] MAC Address
This Section will display the unique12 digit, hexadecimal number assigned as the Media Access Control (MAC) address of the device.
System Reset Defaults
[999] Software Default
Default (99);
The Software default allows the installer to refresh the unit after changes and also return the Communicator to the default state.
00: Default Module. All programming Sections in module are rolled back to factory settings.
CAUTION: This will erase ALL existing programming of the unit.
55: Reset. The Communicator is reset. This option is equivalent to power cycling the Communicator.
NOTE: The installer should perform a module reset after any Sections have been changed by keypad programming.
Programmed Minutes
Table 10: Ethernet Test Transmission Interval
Daily
Weekly
001440
010080
11
Monthly
043200