Special requirements for R32
Do NOT have refrigerant leakage and open flame.
Be aware that the R32 refrigerant does NOT contain an odour.
The appliance shall be stored so as to prevent mechanical damage and in a well-ventilated room without
continuously operating ignition sources (example:open flames,an operating gas appliance) and have a room size
as specified below.
Do NOT re-use joints which have been used already.
Joints made in installation between parts of refrigerant system shall be accessible for maintenance purposes.
Make sure installation,servicing,maintenance and repair comply with instractions and with applicable legislation
(for example national gas regulation) and are executed only by authorised persons.
Pipework should be protected from physical damage.
Installation of pipework shall be kept to a minimum.
If the total refrigerant charge in the system is <1.84 kg (i.e. if the piping length is <20m for 8/10kW), there are no additional
minimum floor area requiements.
If the total refrigerant charge in the system is ≥1.84 kg (i.e. if the piping length is ≥20m for 8/10kW), you need to comply with
additional minimum floor area requirements as describrd in the following flow chart. The flow chart uses the following tables:
"Table 1-Maximum refrigerant charge allowed in a room: indoor unit" on page 5, "Table 2-Minimum floor area: indoor unit" on
page 5 and "Table 3-Minimum venting opening area for natural ventilation: indoor unit" on page 5.
If the piping length is 30m,then the minimum floor area is ≥4.5m
of 200cm
.
2
WARNING
WARNING
NOTE
WARNING
NOTE
;if the floor area is less than 4.5m
2
A
a
a Indoor unit
A Room where the indoor unit is installed.
B Room adjacent to room A.
The area of A plus B has to be greater than or equal to 4.5 m
03
,it need to trepanning a hole
2
B
VA
min
VA
min
.
2
V.2