Warning
All of the operations described in this section must be performed by professionally qualified personnel only.
5.1. INSTALLATION ON FLOOR OR CEILING
The space heater can be installed on a support base, which must be:
• stable and horizontal
• made of non-combustible material
Accessories include support hooks to suspend the heater by hooking it to the ceiling with ropes and/or chains of
appropriate capacity and length, to be attached to the four suspension points
Warning
Make sure that the ropes and/or chains form an angle not more than 5° with vertical to the ceiling, that the
ropes do not cross, and that a different rope is used for each hook.
The minimum distance from surrounding walls, floor and/or ceiling must be at least 1 m and the distance from the
floor of at least 500 mm.