Essential Circuits
Consult with owner to clearly identify the circuits in
building that are "essential".
It is important that you understand which circuits the
owner wants to include as "Essential Circuits". Depending
on the power consumed by these circuits, most or all of
them can be switched to the Home Generator System for
the duration of normal power interruption.
The wattage reference guide shown in Figure 2 will assist
the owner with their decision-making process. It provides
the wattage used by many ordinary household devices. Use
it as a guide when selecting essential circuits. Review this
information with the owner and convey any technical
considerations that might affect the cost of installation.
Essential Circuit Selection
When selecting the essential circuits that will be switched to
"Standby Power, " it is important that the sum of the combined
circuit loads does not exceed the wattage/amperage capacity
of the generator.To help you with your selection of essential
circuits, please consider the following:
Add up the total wattage of all electrical devices to be
connected at one time.This total should NOT be
greater than the generator's wattage capacity.
The rated wattage of lights can be taken from light bulbs.
The rated wattage of tools, appliances and motors can
usually be found on a data plate or decal affixed to the
device.
If the appliance, tool or motor nameplate does not list
wattage, multiply volts times the ampere rating to
determine watts (Volts x Amps = Watts).
Some electric motors (induction types) require about
three times more watts of power for starting than for
running.This surge lasts for only a few seconds. Be sure
you allow for this high starting wattage when selecting
electrical devices that will be energized by the Home
Generator System:
•
Figure the watts required to start the largest motor.
•
Add that to the total running watts of all other
connected loads.
This Briggs & Stratton Home Generator System
complies with the following "stationary standby
power rating":
The standby power rating is applicable for supplying power
for the duration of normal power interruption. NO
sustained overload capability is available for this rating.
INSTALLATION
Figure 2 — Wattage Reference Guide
Device
Air Conditioner (12,000 Btu)*
Air Conditioner (24,000 Btu)*
Air Conditioner (40,000 Btu)*
Battery Charger (20 Amp)
Circular Saw (6-1/2")
Clothes Dryer (Electric)*
Clothes Dryer (Gas)*
Clothes Washer*
Coffee Maker
Compressor (1 HP)*
Compressor (1/2 HP)*
Compressor (3/4 HP)*
Curling Iron
Dehumidifier*
Electric Blanket
Electric Range (per element)
Electric Skillet
Freezer*
Furnace Fan (3/5 HP)*
Garage Door Opener*
Hair Dryer
Hand Drill
Iron
Jet Pump*
Light Bulb
Microwave Oven
Milk Cooler*
Oil Burner on Furnace
Oil Fired Space Heater (140,000 Btu)
Oil Fired Space Heater (30,000 Btu)
Oil Fired Space Heater (85,000 Btu)
Radio
Refrigerator
Slow Cooker
Submersible Pump (1 HP)*
Submersible Pump (1/2 HP)*
Submersible Pump (1-1/2 HP)*
Sump Pump*
Table Saw (10")*
Television
Toaster
*Allow three (3) times listed watts for starting device
10
Running
Watts
1700
3800
6000
500
800 to 1000
5750
700
1150
1750
2000
1400
1800
700
650
400
1500
1250
700
875
500 to 750
1200
250 to 1100
1200
800
100
700 to 1000
1100
300
400
150
225
50 to 200
700
200
2000
1500
2800
800 to 1050
1750 to 2000
200 to 500
1000 to 1650