Descargar Imprimir esta página

Hisense Hi-Therma Serie Manual De Instalación Y Mantenimiento página 24

Ocultar thumbs Ver también para Hi-Therma Serie:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 83
PIPING WORK
(2) Install shut-off valves
A shut-off valve and a shut-off valve with filter are provided
with the unit. For convenience of repair and maintenance,
install the shut-off valve with filter on water inlet pipe and the
shut-off valve on water outlet pipe of indoor unit as follow.
Water
Gaskets
inlet
?
N O T E
The shut-off valve can connect to the water inlet of indoor unit directly.
The shut-off valve with filter must be installed at water inlet of indoor
unit, and water flow direction and installation direction must be
confirmed as shown below. The gasket in accessories can be installed
at the two connections of shut-off valve and shut-off valve with filter.
!
C A U T I O N
Rubber gasket must be mounted (accompanied with the unit),
otherwise water leakage may be caused.
Note the location of shut-off valves, and the direction of shut-off
valves and drain valve, which are essential to maintenance.
Screw up shut-off valves by using two wrenches.
Liquid
Gas
Water
pipe
pipe
outlet
(3) Additional water strainer
!
C A U T I O N
Provide a 50 mesh or more water strainer at the water inlet side of
water piping. Otherwise, damage to the plate heat exchanger may
occur. In the plate heat exchanger, water flows through a narrow
space between the plates.Therefore, there is a possibility that
freezing or corrosion may occur if foreign particles or dust clog the
flow of water between the plates.
This is not required when cooling mode is not used.
Water Flow Direction →
The water piping connection needs to be completed after flushing
the water system
12
Water Strainer
(50 mesh or more recommended)

Publicidad

loading