To position the unit, follow the operations described below:
Step
1
Fit the 4 feet (included in the bag supplied) which allow the
unit to be stabilized on floors that are not perfectly flat.
Note: To fit and/or adjust the height of each foot, tilt the unit
as necessary at the place involved in leveling.
Strictly respect the safety distances from combustible materials to avoid serious
damage to people's health and the integrity of the home.
The sealed unit can also be installed in domestic environments with the presence of forced ventilation (e.g.
extractor hoods) or rooms that may be in a negative pressure with respect to the outside.
A summary table of the minimum distances to be respected is shown below:
d
C
ELDA 7 - CORONA 7
800 mm
ELDA 9/11 - CORONA 9/11
This distance must be in free air
1
Floor
2
Minimum distance for frontal radiation
3
Radiation area
4
Vertical walls
5
Area to protect
d
Minimum distance from ceiling
C
NOTE. The definitions of the distances are taken from UNI EN 16510-1.
If the floor is made of wood or other combustible material, use a protection in non-combustible material (steel, glass,
etc.) which also protects the front part from possible falling of combustible materials during cleaning operations.
If the floor is made of combustible material, always install a floor protector.
EN
Action
d
d
F=
P
..................... 800 mm
........ 1000 mm
A73023860 - Rev 01 - 06/2023
d
d
d
B
R=
S
2000 mm (se d
0 mm
200 mm
0 mm (se d
d
Minimum frontal distance from floor
F
d
Minimum frontal distance from objects
P
d
Minimum distance from floor below
B
d
Minimum distance from rear objects
R
d
Minimum side distance
S
d
Minimum side distance in radiation area
L
Image
d
L
≤1500 mm)
S
>1500 mm)
S