Connecting The Output Module Load Supply - Aventics RMV04-8DI M8 Instrucciones De Servicio

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 155
56
AVENTICS | EtherNet/IP™ | R412012728–BDL–001–AC
Assembly
O0...O7
4
3
1
1
2
5
4
3
Table 11:
Output assignment for 8x output module, DO8_M8, M8x1 socket
Pin
Signal
1
Free
4
Ox
3
GND
Housing
Table 12:
Output assignment for 8x output module, DO8_M12, M12x1 socket
Pin
Signal
1
NC
2
O1, O3, O5 or O7
3
GND
4
O0, O2, O4, or O6
5
NC
Housing
Total current is too high
Every output is supplied with a continuous current of max. 0.5 A. Current loads
over 0.5 A per output can damage the system.
Make sure that the current load of 0.5 A per output is not exceeded.
6.3.5

Connecting the output module load supply

Each output module has its own M12 connection for the load supply. Each of the
4 outputs are supplied via the load supply. The U
isolated.
The connection cable for the output module load supply must meet the following
requirements:
Cable socket: M12x1, 4-pin, A-coded without center hole
(to ensure correct plug-in connection)
Cable cross section: > 0.5 mm
Length: Max. 20 m
1. Set up the correct pin assignment (see tab. 13) on the plug connections
if you do not use pre-assembled cables.
2. Connect the load supply using the M12 plug.
Assignment
Not assigned
Ox output signal
(nominal voltage 24 V)
GND actuator reference
Connected to shield potential
Assignment
Not assigned
Output signal
Reference potential
Output signal
Not assigned
Connected to shield potential
NOTICE
and U
Q1
Q2
2
per wire
voltages are galvanically