Chapter 4 - SettING the SSW-07
32
Motor
Current
3xIn
5xIn
7xIn
table 4.1 - Motor protection thermal class time in cold condition at S.F.=1
Motor
Current
3xIn
5xIn
7xIn
table 4.2 - Motor protection thermal class time in cold condition at S.F.=1.15
NOTES!
When SSW-07 is without the electronic supply voltage (A1 and
A2), the thermal image is saved internally. When the supply (A1
and A2) is re-established, the thermal image value returns to the
value prior to the electronic supply loss.
The RESET of the electronic overload protection can be set
to manual function (man). In this case the RESET must be
made via digital input 2 (DI2) or through the RESET key. If the
RESET setting is set to automatic (auto), the fault condition will
automatically be reset after the equipment cooling time;
Upon disabling the electronic overload protection, the thermal
image is reset at zero.
Class
30
20
101.2 s
67.5 s
33.7 s
36.1 s
24 s
12 s
18.3 s
12.2 s
6.1 s
Class
30
20
135.1 s
90.1 s
45.1 s
47.7 s
31.8 s
15.9 s
24.3 s
16.2 s
8.1 s
10