6.1
Electrical system (factory set)
Burners RL 70 - RL 100 - RL 130
Models RL 70 - 100 - 130 leave the factory preset for 400 V
power supply.
If 230 V power supply is used, change the motor connection
from star to delta and change the setting of the thermal cut-
out as well.
Key to wiring diagram (Fig. 15)
CMV
- Motor contactor
FR
- Photoresistor
I1
- Switch: burner off - on
I2
- Switch: 1st - 2nd stage operation
MB
- Terminal strip
MV
- Fan motor
RMO88.53A2
- Control box
RT
- Thermal cut-out
TA
- Ignition transformer
TB
- Burner ground (earth) connection
V1
- 1st stage solenoid valve
V2
- 2nd stage solenoid valve
VS
- Safety solenoid valve
XP1
- Connector for STATUS
NOTE:
For remote-reset, connect a push-button switch (NO) be-
tween terminal 3 and neutral of the control box (terminals 15,
16, 17 and 18).
Electrical system
6.1.1
Electrical connections (Fig. 16)
Set up by the installer
Use flexible cables according to regulation EN 60 335-1:
if in PVC boot, use at least H05 VV-F
if in rubber boot, use at least H05 RR-F.
All the cables to be connected to the burner terminal strip 8)(Fig.
16) must be routed through the fairleads.
The fairleads and precut holes can be used in various ways. One
example is given below:
1
Pg 13,5
2
Pg 11
3
Pg 11
4
Pg 9
5
Pg 9
6
Pg 11
7
Pg 13,5