Descargar Imprimir esta página

Danfoss AAF 007 Guia De Instalacion página 5

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 20
Advanced Active Filter AAF 007
Installation Guide
1 Installation
1.1 Safety and Installation Awareness
Both an installation guide and a safety guide are provided with the filter. Before starting installation, get familiarized with all safety
guidelines and precautions in the safety guide.
The Advanced Active Filter AAF 007 is not intended for service and repair outside the factory. Malfunctioning units must be re-
placed and returned to the factory.
1.2 Intended Use
The Advanced Active Filter AAF 007 is intended to be used in electrical installations to improve power quality. To achieve an im-
proved power quality, the filter injects currents in counter-phase to mitigate distortions on the grid.
1.3 Required Tools
Tape measurer
Slotted screwdrivers (SL1/SL2)
PH1, PH2 screwdrivers
Wrench with extender and 10 mm (for wall mounting)
Cable strip
Wire crimper for mains cable
1.4 Electrical and Mechanical Ratings
137G3607
Mains supply
3x380–480/277 V / 50–60 Hz
Mains type
TN, TT, IT (non-corner grounded)
Current
0–35 A
Ambient temperature
Minimum -10 °C (14 °F)
Maximum 50 °C (122 °F)
Derating above 40 °C (104 °F)=-3%/K (up to 50 °C
(122 °F))
Ploss
556 W
Weight
16 kg (35.3 lb)
Dimensions (HxWxD)
510x106x360 mm (20.1x4.2x14.2 in)
SCCR
5 kA
1.5 Verifying the Shipment and the Contents
Ensure that the items supplied and the information on the nameplate correspond to the order confirmation. The filter module label
is on the top of each filter module.
Danfoss A/S © 2023.01
137G3610
3x380–480/277 V / 50–60 Hz
TN, TT, IT (non-corner grounded)
0–55 A
Minimum -10 °C (14 °F)
Maximum 50 °C (122 °F)
Derating above 40 °C (104 °F)=-3%/K (up to 50 °C
(122 °F))
833 W
17 kg (37.5 lb)
510x106x360 mm (20.1x4.2x14.2 in)
5 kA
AN43084697267901-000101 / 130R1374 | 5
Installation

Publicidad

loading

Este manual también es adecuado para:

137g3607137g3610