Advanced Active Filter AAF 007
Installation Guide
2
2 × 2m × 1 . 5 × 5
× 0 . 01786 Ω × m
A =
2
2 . 5 VA × mm
1.9 Four-wire System
All descriptions in the previous sections and following illustrations are targeting 3-wire systems. The filter can also operate in 4-wire
systems. Additional to the steps already described and illustrated, the following must be done:
rd
•
A 3
CT must be installed on phase 2/phase B.
•
The Neutral wire must be connected to the mains terminal.
•
In the PC tool for the filter, adjust the grid topology to 3P4W.
FILTER MALFUNCTION
Connecting the neutral wire in 3-wire applications will cause the filter to work improperly.
-
Do not connect the neutral wire in 3-wire applications.
1.10 Power Losses and Efficiency
For power loss data including part load losses, see https://ecosmart.mydrive.danfoss.com.
1.11 Cable and Fuse Specifications
The filter is protected internally with semiconductor fuses. Branch protection is subject to local installation conditions and regula-
tions, and thus no recommendations can be made. To support selection of suitable branch protection, the internal fuses of the filter
are specified in the following table.
L1/L2/L3 cross-section
Maximum stripping
Torque
Material
Temperature rating
PE cross-section
Maximum stripping
Cable lug
Torque
Material
Temperature rating
CT cables cross-section
Torque
Control cables cross-section
Danfoss A/S © 2023.01
2
= 1 . 07 mm
N O T I C E
35 A module
2
Rigid: 2.5–35 mm
(2 AWG)
2
Flexible: 2.5–25 mm
(14–4 AWG)
Flexible with ferrule: 2.5–25 mm
18 mm (0.7 in)
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
16 mm
(6 AWG)
18 mm (0.7 in)
O-type 5–6 mm
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
2.5 mm
(14 AWG)
0.8 Nm (7.1 in-lb)
2
1 mm
(17 AWG)
55 A module
Rigid: 2.5–35 mm
Flexible: 2.5–25 mm
2
(14–4 AWG)
Flexible with ferrule: 2.5–25 mm
18 mm (0.7 in)
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
16 mm
(6 AWG)
18 mm (0.7 in)
O-type 5–6 mm
2.5–3.0 Nm (22.12–26.5 in-lb)
Copper
70 °C (158 °F)
2
2.5 mm
(14 AWG)
0.8 Nm (7.1 in-lb)
2
1 mm
(17 AWG)
AN43084697267901-000101 / 130R1374 | 9
Installation
2
(2 AWG)
2
(14–4 AWG)
2
(14–4 AWG)