Installation Instructions – Sure-Lites SELRA50 / SELRA50SD Recessed Emergency Light
Instruction for Self-Diagnostic Test:
Once the unit is properly installed according to the installation instruction sheet and AC power supplied, the dual color
LED indicator will come ON and the self-diagnostic test function will automatically initiate. The Unit will switch into a load
calibrating mode for 5-10 seconds to record the connected load. Lampheads will turn ON during this step. Once done, the
LED indicator will show a RED/GREEN flashing status. This indicates that the unit is in Hi-Charge mode. A STEADY GREEN
LED indicates normal service; FLASHING GREEN indicates the unit is testing; GREEN/RED FLASHING indicates the battery
is charging; RED (in different combinations) would indicate a service alert. Refer to the SERVICE INDICATION chart below for
more details. The LED will be OFF when the unit is in emergency mode.
During a manually-initiated test OR monthly/annual self-diagnostic test, if the calibrated load is not detected, then the LED
indicator will flash FOUR times, indicating a load failure error. This error code can be reset by pressing and holding the test
switch for at least (6) seconds, allowing the unit to calibrate the load again.
Self-Diagnostic Service
The self-diagnostic function is factory preset and performs the following:
a.
Monitoring of battery, battery charger, and lamps (both local and remote lamps when applicable )
b.
Self-testing and a 30-second or longer discharge once every 30 days, after AC power has been supplied for a minimum
of 24 hours.
c.
Self-testing and a 30 -minute or longer discharge once every 180 days, after AC power has been supplied for a minimum
of 24 hours.
d.
Self-testing and a 90-minute discharge once every 365 days, after AC power has been supplied for a minimum of 24 hours.
Service Indication
LED Indicator
One flash Red
Two flash Red
Four flash Red
Steady Red
Solid Green
Flashing Green
Red/Green Flashing
Manual Testing
The unit also provide for manual testing by pushing the test button in a specific pattern.
Action
Push test button One Time (within 2 seconds)
Push test button Two Times (within 2 seconds)
Push test button Three times (within 2 seconds)
Push test button and hold for 3 seconds (While in test
mode)
Push test button and hold for 6 seconds
(While in test mode)
Warning:
a) Make sure that power is OFF before making any electrical connections.
b) Unused wires must be capped using enclosed wire nuts.
4
COOPER LIGHTING SOLUTIONS
LED Indicator Status
Circuit Fault
Battery Fault
Lamp or Load Fault
Battery Disconnected
Trickle Charge
Test Mode
Hi-Charge
IB50507322
Installation Instructions
Reaction & LED Indication
30-second test: FLASHING Green
30-minute test: Green FLASHING twice
90-minute test: Green FLASHING three times
Cancels test. If self-test is cancelled it is recommended
that a manual test of the same duration be performed
at a more convenient time to ensure compliance
System reset