ARES UPS User Manual
Model
AC Inverter Supply
Battery Supply
Bypass Supply
Efficiency Full Linear Load
Line mode
Rating 230Vac
Battery mode
Rating 230Vac
ECO mode
Rating 230Vac
Battery
Number of batteries
Battery type
50% Load
Backup time
70% Load
(Linear Load)
100% Load
230V – 1K
<105� continuous
106-120% for 30 seconds transfer to bypass
121-150% for 10 seconds transfer to bypass
>150% Immediately transfer to bypass.
Buzzer continuously alarms.
<105% continuous
106-120% for 30 seconds shuts down
121-150% for 10 seconds shuts down
>150% Immediately shuts down.
Buzzer continuously alarms.
<105% continuous
106-120% for 250 seconds shuts down
121-130% for 125 seconds shuts down
131-135% for 50 seconds shuts down
136-145% for 20 seconds shuts down
146-148% for 5 seconds shuts down
149-157% for 2 seconds shuts down
158-176% for 1 seconds shuts down
177-187% for 0.32 seconds shuts down
>188% for 0.16 seconds shuts down
Buzzer continuously alarms
>90%
>86%
>96.5%
3
12 V/7.2Ah
10min 30sec
10min 30sec
6min 30sec
6min 30sec
4min
230V – 2K
230V – 3K
>91%
>91.5%
>86%
>86%
6
12 V/9Ah
6min
3min 30sec
4min
2min
6
21