MANUTENZIONE
Procedura di verifica per diodi rotore
eccitatrice HCP3.
Strumentazione necessaria :

batteria 12V

lampada 12V-21W (o in alternativa
resistenza 6.8-30W)

voltmetro (Ex. Multimetro su scala
VOLT d.c.)
Importante: Prima di eseguire le
operazioni seguenti sconnettere i due
cavi
di
collegamento
principale al ponte diodi (+ e -).
TEST DEI DIODI SUL "NEGATIVO"

Connettere
gli
strumenti
indicato in figura A (tabella 7 pag.
48)

Fissare
il
cavo
connesso
lampada al morsetto negativo del
ponte come indicato in figura A
(tabella 7 pag. 48)

Connettere il terminale "Probe" ai
punti A1, A2 ed A3 in sequenza per
verificare rispettivamente i diodi 1, 2
e 3. Verificare la lettura sul voltmetro
in relazione a quanto indicato in
tabella (tabella 7 pag. 48).
TEST DEI DIODI SUL "POSITIVO"

Connettere
gli
strumenti
indicato in figura B (tabella 7 pag.
48)

Fissare il cavo connesso al negativo
della batteria al morsetto positivo del
ponte come indicato in figura B
(tabella 7 pag. 48)

Connettere il terminale "Probe" ai
punti A4, A5 e A6 in sequenza per
verificare rispettivamente i diodi 4, 5
e 6; verificare la lettura sul voltmetro
in relazione a quanto indicato in
tabella (tabella 7 pag. 48).
ISTRUZIONI PER LA SOSTITUZIONE
DEL DIODO.
Qualora i valori riscontrati indichino un
diodo
danneggiato,
procedere
alla
sostituzione
componente.
A tale scopo si raccomanda di non
estrarre i reofori dalle rispettive sedi ma
di tagliarli in prossimità del corpo del
componente;
inserire
componente rispettando le polarità e
saldare a stagno accuratamente i reofori
con gli spezzoni rimasti nelle sedi.
del
rotore
-
come
alla
+
come
occorrera'
del
il
nuovo
IMPORTANTE
IMPORTANT
WICHTIG
34
MAINTENANCE
Procedure to check the diodes of the
HCP3 exciter rotor.
Necessary equipment :

12V battery

12V-21W lamp (or alternatively 6.8
-30W Resistance)

Voltmeter (for instance, multimeter
on scale VOLT d.c.)
Warning:
before
performing
following actions, it is necessaty to
disconnect the 2 cables connecting
the main rotor to the diode bridge
(+and-)
TEST OF THE DIODES ON THE
"NEGATIVE"

Connect the equipment, as it is
pointed out in the picture A (table 7
page 48)

Fix the cable connected to the lamp
to the negative terminal of the
bridge, as it is pointed out in the
picture A (table 7 page 48)

Connect the terminal "Probe" to the
point A1 (it is checked the diode 1),
then to the point A2 (it is checked the
diode 2) and finally to the point A3 (it
is checked the diode 3); check the
readings on the voltmeter in relation
with what is reported on the table
(table 7 page 48).
TEST OF THE DIODES ON THE
"POSITIVE"

Connect the equipment, as it is
pointed out in the picture B (table 7
page 48)

Fix the cable connected to the
negative terminal of the battery to
the positive terminal of the bridge, as
it is pointed out in the picture B (table
7 page 48)

Connect the terminal "Probe" to the
point A4 (it is checked the diode 4),
then to the point A5 (it is checked the
diode 5) and finally to the point A6 (it
is checked the diode 6); check the
readings on the voltmeter in relation
with what is reported on the table
(table 7 page 48).
INSTRUCTIONS TO REPLACE
THE DIODE
When the values measured point out a
diode damaged, it is necessary to
replace the component.
For this purpose it is recommended to
not pull the rheophores out from their
locations, but to cut them near to the
body of the component; then fit in the
new component respecting the polarity
and
soft-solder
accurately
rheophores with the pieces remained in
their locations.
HCO-HCP MANUAL July 2016 Revision 04