Table 3.2: Configuration of the switches to select the type of analog input and output signal on the CFW500-IOS
Input/
Signal
output
Voltage
AI1
Current
Voltage
AO1
Current
NOTE!
Configuration to connect the RS485:
S1.3 = ON and S1.4 = ON: terminal RS485 ON.
S1.3 = OFF and S1.4 = OFF: terminal RS485 OFF.
Any other combination of the switches is not allowed.
For the correct connection of the control, use:
1) Gauge of the cables: 0.5 mm² (20 AWG) to 1.5 mm² (14 AWG).
2) Maximum torque: 0.5 N.m (4.50 lbf.in).
3) Wiring of the plug-in module connector with shielded cable and separated from the
other wiring (power, command in 110 V / 220 Vac, etc), according to
Separation
Distance. If those cables must cross other cables, it must be done in
perpendicularly among them, keeping the minimum separation distance of 5 cm at
the crossing point.
Connect the shield according to the figure below:
4) Relays, contactors, solenoids or coils of electromechanical brake installed close
to the inverters may occasionally generate interference in the control circuitry. To
eliminate this effect, RC suppressors (with AC power supply) or freewheel diodes
(with DC power supply) must be connected in parallel to the coils of these devices.
5) When using the external HMI (refer to
to the inverter must be separated from the other cables in the installation, keeping
a minimum distance of 10 cm.
6) When using analog reference (AI1) and the frequency oscillates (problem of
electromagnetic interference), interconnect the GND of the connector of the plug-in
module to the inverter grounding connection.
Setting of
Signal
switch S1
range
S1.1 = OFF
0...10 V
0...20 mA
S1.1 = ON
4...20 mA
S1.2 = ON
0...10 V
0...20 mA
S1.2 = OFF
4...20 mA
Inverter
Side
Figure 3.5: Connection of the shield
section 7.2
- English -
Installation and Connection
Parameter setting
P0233 = 0(direct reference) or 2 (inverse reference)
P0233 = 0(direct reference) or 2 (inverse reference)
P0233 = 1(direct reference) or 3 (inverse reference)
P0253 = 0(direct reference) or 3 (inverse reference)
P0253 = 1(direct reference) or 4 (inverse reference)
P0253 = 2(direct reference) or 5 (inverse reference)
Insulate with Tape
Do Not Ground
Accessories), the cable that connects
item 3.2.6 Cable
CFW500 | 17