UM_s-MEXT_ME28relC_00_12_19_ML
Maska terminalu
--------------- P50.01
Set point cooling:
24.0 °C
--------------- P50.02
Set point heating:
24.0 °C
--------------- P50.03
Set point dehumidif.
55%RH
--------------- P50.04
Set point humidif.:
45%RH
--------------- P50.05
Set point cooling by
LAN limits:
30.0°C
--------------- P50.06
Set point heating by
LAN limits:
18.0°C
--------------- P50.07
Set point dehumdif. by
LAN limits:
75%RH
--------------- P50.08
Set point humdif. by
LAN limits:
35%RH
--------------- P50.09
MIN room temperature
for deumid OFF: 23.0°C
Clock
Clock card
not installed
Clock config.:
Date
Tme
01/05/13
10:40
Time bands
not enabled.
See user menu
PODRĘCZNIK UŻYTKOWNIKA
Opis maski
Parametry do ustawiania Setpoint zimna
i Setpoint ciepła jeżeli są uaktywnione zasoby ciepła
Parametry do ustawienia Setpoint odwilżania
i Setpoint nawilżania
Parametry do ustawienia Setpoint zimna dla granic LAN
i Setpoint ciepła dla granic LAN
Parametry do ustawienia Setpoint odwilżania dla granic LAN
i Setpoint nawilżania dla granic LAN
Parametry dla minimalnej temperatury otoczenia do wyłączenia odwilżania
Maska dokonanego dostępu do menu Clock.
Nacisnąć klawisze "Up" lub "Down" w celu przesuwania się po innych maskach, "Esc" w celu powrotu do menu.
Podmenu, które pozwala wyregulować wewnętrzny zegar i skonfigurować zakresy godzinowe.
Maska wskazująca nieobecność lub uszkodzenie karty zegara.
Ustawienie aktualnej daty i godziny.
Wskazuje, że zakresy godzinowe są ustawione prawidłowo, ale nie są uaktywnione. W celu ich uaktywnienia,
patrz menu użytkownika.
347